Lec 53: Three-Phase Load Flow (Derivation of J9)

IIT Roorkee July 201
61 followers
Sep 27, 2024
In this lecture, the derivation of the general expressions for the elements of J9 is discussed.
Hello, welcome to this lecture on Modeling Analysis and Estimation of Three-Phase
Unbalanced Power Network. So, we have been talking about the derivation of the Jacobian
matrix elements. So, we have so far covered first two row. So, let us now try to recapitulate.
So, what we had is that our Jacobian structure is something like this del p, del q,
del pj, del v specified. So, this is our Jacobian matrix. So, this is our mismatch vector
14, 16 and then we have delta theta, delta v, delta theta internal, del v internal.
So, this is what is our Jacobian matrix structure. Of course, all these are. So, then therefore,
now all this j1, j2, j3 up to j16 these are nothing but the Jacobian sub matrices. So,
far we have looked into detail the derivation of the elements of the matrices j1 to j8. So,
now today we will start looking into the matrices j9, j10, j11 and j12.
So, then therefore, j9 would be from this del pj, of course this is a vector, all these are vector,
all these are vector, all these are vector, del pj by del theta, j10, j10 would be del pj by del v,
j11 would be del pj by theta internal and j12 is del pj by del v internal.
Of course, now we have already looked into the vectors theta, v, theta internal, v. So,
then we are not going to repeat it. What is the vector p gen? p gen vector is p gen 1,
p gen 2 dot dot dot p gen m transpose. So, what is p gen i? p gen i is the real power
generation, I am wrong here, it would be not p gen, this would be p gen 2, p gen 3.
p gen i is real power generation, I should say total, real power generation at
generator i. Generator i means is actually in our parlance that the generator connected at
bus i. Please note that in our case, we have assumed that all the m generators,
they are connected at the first m buses of the system. So, generator connected,
and so then therefore, this vector is m minus 1 cross 1, that is obvious because there are m minus
1. Why this p gen 1 is not there? Because we said that there would be one generator which would be
acting as a slack bus. So, then therefore, for that particular slack bus, we really cannot
pre-specify the total real power generation until unless you solve the load flow program.
So, now we have to, so then therefore, so now if we have to take, so then therefore,
J 9 would be basically and we said that, so then therefore, J 9 for example, J 9 would be looking
like this, del p gen 2 by del theta 1 b, then del p gen 2 by del theta 1 c dot dot dot del p gen 2
by del theta n c, right. Then the second row would be del p gen 3 by del theta 1 b, then del p gen 3
by del theta 1 c dot dot dot del p gen 3 by del theta 1 c. So, all this we will go and then last
row would be del p gen m by del theta 1 b, then del p dot dot dot gen m by del theta 1 c
dot dot dot del p gen m by del theta 1 c. The reason for this that we again recollect
that this theta vector is essentially theta 1 b, theta 1 c, then theta 2 a, then dot dot dot
theta n b, theta c, right. And we again note that the generation 1,
theta 1 a is equal to 0, it is the reference angle and generator 1 is this lag bus,
generator 1 is this lag bus. So, then obviously, so now to derive these elements,
we have to now essentially write down the expression of p gen i. So, now let us look at
what would be the expression of p gen i. Now, let us recollect one simple fact.
Now, let us take an example to again let us say n is equal to 5, m is equal to 3, let us just. So,
let us say that this is the structure. So, these are important. So, let us say that this is bus 1,
this is bus 2, this is bus 3, this is bus 4, this is bus 5 and at bus 1 there is one generator
and bus 2 there is another generator and at bus 3 there is another generator. So,
n is equal to 5 that is there are total 5 buses in the system and there are 3 generators.
And we know that this system is being augmented by, so it is being augmented by
internal buses. So, these are the original buses, these are the original buses
and now I have got internal bus. So, here also I have got internal bus
and my generator is actually connected here. Now, I also have an internal bus
and this is and these are the original lines. So, these are right. So, the bus number is 1,
then this is 4, then this is 2, then this is 5, then this is 3 and then we said that this would
be 6, this will be 7, this will be 8. That was the kind of convention for naming the or rather
for actually numbering the internal buses we have adopted. So, that means the internal bus number
would be i plus n, right. So, internal bus number is, so internal bus corresponding to
ith generator is n plus i, right. So, this is the convention we have followed.
Now, here in this case, now here we are actually talking about, now for this system
my p gen vector is p gen, my p gen vector is actually p gen 2 and p gen 3 that is my
p gen vector, okay. Now, we also said that when we are actually
creating the internal bus for our convenience, we are also shifting the position of the generator
from the original bus to the internal bus. So, my generators are now connected here as if.
This creates no problem as far as the real power is concerned because we have assumed that this
one is the, essentially this is purely reactive. So, then therefore there is no real power loss.
So, then therefore whatever real power is being injected here, this entire real power is also
arriving at bus 1, right, which is also the case in the original case.
So, then therefore p gen 2 is nothing but is equal to p 7. So, then therefore in our case,
I can say that by looking at this p gen 2 is nothing but is equal to p 7 and p gen 3.
Now, please note that this total p gen 2 is nothing but the total 3-phase power generated
by this generator. Now, the total 3-phase power generated by this generator would be,
that would be is equal to power generated at phase a that is p 7 a plus p 7 b plus p 7 c.
What is p 7 a? p 7 a is the real power injected by this generator
at bus 7 corresponding to phase a, right. Similarly, p 7 b is real power injected
at generator at bus 7 corresponding to phase b and this is at corresponding to phase c, right.
So, let us write that p ip, it is our, you know, usual notation we are actually following.
Similarly, p gen 3 would be here p 8 a plus p 8 b plus p 8 c, right. So, it would be p 8 a plus p 8
b plus p 8 c. Because you see, total real power generated by any generator is nothing but the sum
total of the real power generated at phase a plus phase b plus phase c. Now, because we have
shifted this generator at bus 2 to bus 7, so then therefore, total real power generated by the
generator at bus 2 would be equal to the total real power generated by the generator located at
bus 7 and total real power generated by the generator located at bus 7 would be equal to the
real power generated at phase a plus real power generated at phase b plus real power generated
connected at phase c. Similarly, for the generator connected at bus 3, correct. So, then therefore,
in general we can say in general, in general, in general, in general, we can say in general.
Now here, you can see that p gen i is equal to p 8 now. So, then therefore, when i is
equal to 3, it is 8, 8 is nothing but 5 plus 3 and basically what is 5? 5 is nothing but
n. So, then therefore, p gen i, p gen i, p gen i, that would be is equal to p n plus
i a plus p n plus i b plus p n plus i c, correct, for and i is n. What is p n plus i a? It is
basically p n plus i p is essentially, it is nothing but, so just let us write down
p n plus i p is the real power injected at bus n plus i at phase p, p is p n plus i a.
Now, what is p n plus i a? Now, what is p n plus i a? Now, p n plus i a is, now I know that p i p,
we have already said that it is L is equal to a b c and then we said that j is equal to 1
to n plus m, then we said that V i p V j L, then we have Y i j p L, then we have cosine
theta i p minus theta j L minus alpha i j p L, right. So, this is the general expression.
So, then therefore, from here I can write down that p n plus i a would be is equal to L is equal
to a b c j is equal to 1 to n plus m V i. So, V n plus i a because i is equal to n plus i and p is
equal to a, then usual V j L Y i in place of i it is n plus i V j, then a, then L cosine theta n
plus i a minus theta j L minus alpha n plus i j a L, right. So, this would be the case.
So, it appears that p n plus i a. So, then therefore, similarly p n plus i b,
similarly the expressions for p n plus i b. Now, let us look at very one very interesting thing.
Suppose, as an example suppose we are trying to write down example suppose we are trying to write
down example n is equal to 5, n is equal to 3 and we are trying to write down say p 7 a, right.
So, if it is p 7 a. So, in this case what will happen L is equal to a b c j is equal to 1 to
n plus m is 8, then V 7 a V j L, then Y 7 j a L cosine theta 7 a minus theta j L minus alpha 7
j a L. So, this would be the case. Now, let us look at a very interesting thing.
Bus 7 is basically directly only connected to bus 2. Bus 7 is not directly connected to at
any other to any other bus. So, then therefore, in the Y bus matrix the quantities Y 7 3, Y 7 1,
Y 7 6, Y 7 5, Y 7 4 as well as Y 7 8, they will be all 0. Only the elements of the bus admittance
matrix corresponding to bus 7 and 2, they will only exist. So, then therefore, Y 7 1 a b c would
be 0, Y 7 6 a b c would be 0, Y 7 8 a b c would be 0, Y 7 3 a b c would be 0, Y 7 4 a b c would be
0 and also Y 7 5 a b c would be 0. Only Y 7 2 a b c would be non-zero, Y 7 7 a b c would be non-zero
and Y 2 2 a b c will be non-zero. Other than these three, they will not exist because they will all
go up to 0. So, then therefore, this J is equal to 1 to 8. So, for 7 1, it would be 0.
When it is 7 2, it would be there. When J is equal to 3, it is 0. When J is equal to 4,
it will be 0. When actually J is equal to 5, it will be 0. When J is equal to 6, it will be 0.
And when J is equal to 7, it will be non-zero. So, it will only be there for only J is equal to 2
and 7. Other than that, all the others, they will not exist. So, then therefore,
this can be simplified as a l is equal to a b c. J will now only have 2 values 2 and 7. Then,
V 7 a V j l Y 7 j V l cosine theta 7 a minus theta j l minus alpha 7 j a l.
So, now it has now become considerably simplified. So, how many terms would be there? There would be
only 6 terms. I mean, basically this one is a single term. So, when I am talking about term,
so we are saying that these are one term. So, these are one term, one single term.
So, there will be essentially only 6 terms, all the other terms. Now, here in this expression,
there would have been 3 into 8 that is basically, actually, theoretically, there would be 24 terms.
But here, because this is an internal bus, these 24 terms, out of these 24 terms, 18 terms will be
all 0, only 6 terms will essentially remain. Similarly, I can say that P 7 b will also be
equal to l is equal to a b c and then here also j is equal to 2 and 7 and then it will be V 7 b,
then V j l Y 7 j V l cosine theta 7 b minus theta j l minus alpha 7 j V l.
In the same way, P 7 c will be similarly, P 7 c will be l is equal to a b c, j would be 2,
7, then it would be V 7 c V j l Y 7 j c l cosine theta 7 c minus theta j l minus alpha 7 j c.
So, then therefore, P gen 2 is equal to P 7 a plus P 7 b plus P 7 c.
So, if I now look at them very carefully, so then it will be essentially l is equal to a b c,
j is equal to 2, 7, then V 7 a V j l Y 7 j l cosine theta 7 a minus theta j l minus
V l plus V 7 c V j l Y 7 j c l cosine theta 7 c minus theta j l minus alpha 7 j c l.
So, that is the P gen 2. So, we stop here with this and then we will continue in the next lecture.
Thank you.