If you’re interested in more business related videos I’m starting to publish them for members. In time I plan on have a full selection on how to manage and complete every step of opening and running a business! Join this channel https://www.youtube.com/channel/UCiz21FXLOV65NTgiUfJsxTg/join
Well guys, ride along with me as I go help one
of my buddies diagnose a system that I don't work on
every day. I mean I was chasing red herrings
and we figured it out though but I'm going to show
you the whole
process
as I'm learning
on the job.
Come with me.
Man I like your
house man I do.
All right so um it's not so I just I had it on emergency heat
and I just turned it to air but
all right so if we just put it
on heat it just blows cold air
right orange on OB this was a two
this is a two-stage yeah
this is two-stage tell you what there's
a number on this I'm gonna set
I'm gonna look that up real quick all right
while that is in its time delay I'm gonna check it
outside and try to pull it at least it's
not um holly bushes it could be
worse yeah holly bushes might look nice but i hate it
when people plant them around their air
conditioning we didn't want things
that stuck most people don't think about it they just oh
that's a nice yeah one thing i don't want
is anything that's going to be sticking everybody
all right i need to see first of all if we have
a call i mean even if it was thinking
it hasn't turned on inside yet okay we got
a five minute delay yeah i think it is a five minute
i hear the deer i hear it too we passed one
on the way in it was just kind of leaned up against
the tree we're moving some of the deer stands around we just got
a late start this year every time I
turned around it was like we set a dime
but we're gonna do it and they'll call up man i gotta change
it all right i'm still waiting for this thing i'm
not sure you said um it's just blowing cold air
I'm not sure it's getting them.
Let me see for if that thermostat is not programmed correctly
That'll happen because you got a heat pump
a two-stage heat pump if it lost its program
It's going to go back to something like um just straight
cool electric heat in that way when your heat comes on
It may not work may not work at all
It may just turn on the fan thinking
the heat strips are on or something
so i'm gonna go what would cause it to lose
the program yeah uh losing power and maybe the
batteries were dead or something if it if it just lost power
for long enough sometimes that happens
well we've lost power periodically
at different times i have a flash you know because storm
uh-huh but yeah me too um i don't think it's got batteries
in it i didn't see any battery
right now i'm checking to see
if this is going to get hot i
do want to see now that i know that
yellow is energized if my orange is energized
this is my orange orange energizes in cool
so orange
should not
be energized
no it is not all
right
so it should
be running
in heat all
right it's time to check pressures which means
we gotta let it time out it did sound like it
was kind
of struggling there
for a second
like pressure
was going real
high there's a true
suction in here i'm gonna get
to right there nope right there
in fact i can get both my pressures
right there yeah now
i remember changing
sensor there's all kinds
of things
that can cause what
what i think hit is high head
pressure that went out kind
of fast we do have an electronic
expansion valve right here
but it looks like it has a bypass valve i'm
not 100 certain that thing
went out on high pressure it could be going out
on low pressure we gotta wait for it to come on
there's something i want to show you
on this this red flash right here
that's a four flash
three excuse me four red flashes
on this EEV board suction temperature sensor input is out
of range replace sensor hmm
it seems like it should still
at least come on i'm pretty sure
this pressure oh sorry this pressure sensor uh i
forget what you call them you can ohm them out
and they have a ohm reading
for the pressure that they're
sensing it all may be right here
so we can tell if it's transducer i'm sorry
that's what i was trying to think of the pressure
transducer we can tell
if it's the transducer
or maybe
that suction line
pressure transducer
j7 that's what we're talking about right here all right
this is for a temperature sensor
pressure transducer okay we know
that our suction pressure right now
is at 86 i hope it tells us
which wires to volts
dc at plug j7 should
be a hold on a second
i got open valve test
i got to figure out how to test it now do i it's
actually looking like i have to plug it back up
and test the volts from this red wire
to that little spot right
there okay according to the
instructions to troubleshoot
this pressure transducer you measure from your red wire
right there actually i'm gonna put this lead
in there and you touch this VP spot and it's going
to give you a voltage
and that is all over
the place i've got one point
i'm just going one from
1.5 to 2.2
and according to that what pressure
is it 99 to you said 1.5 or what like 2.2 2.2
and we're going from 95 to 169 that 169 is kind of high
but the 95 is close to what we're actually
at i'm gonna try
that again all right
now i got 3.5 i'm
gonna see something
if i can all right
That is staining. Let's see if I can test just like this.
No, no.
You're not running a complete circuit, right?
No, no, that ain't gonna work.
But you can ohm across there.
Uh-huh.
And see what your ohm readings are.
Does it have a table for that?
No, but I'm just kind of curious as to what it might be reading.
Because on a transducer,
it should be 30 or 50 ohms.
We're gonna go from red.
Let's try black and get there.
I'll tell you what, I got
better access right here.
once again switch it
to the right thing open lead open lead
open lead i'm not reading any ohms
check your other one with that one
in there you got three wires uh-huh nothing you get no reading
across that thing at all you should
be getting reading something i agree i agree it's just a
coil let me try that again one of my leads was
not shoved in a meter very well all right we're
gonna try dc voltage all right
i'm getting a steady 3.49
that's way out of range isn't it
so if we're like at 90 psi what should we
be reading 90 you'd be at like 1.4 i think that's
our problem i'm glad it's not the EEV
so we know what we need we need a pressure transducer
these fan
blades can
be a little
better put
them down
straight
and drop the
screw a tall
condenser without that little magnet i would have crawled down
in there yeah and that would have been
me it'd be on the
screws wait
a minute here's
one i know the
plastic caps
from this one
let's drop
to another one anyway let's put
the one that's missing one all
the way over here by the house
less likely to be seen i do hope you all enjoyed
the video if you did how about like and subscribe
check out some links in the description some interesting stuff in there
I'll catch you on the next one.