If You’e In The Albany/Leesburg area of South Georgia and wish to set up an appointment, https://clienthub.getjobber.com/hubs/b20c8ec9-030a-4d13-baba-aa8a3d21a5b2/public/requests/4981900/new #hvac#airconditioning#airconditioner#hvacguy @ACIQComfort @Jobber @HVACRSurvival @MilwaukeeTool @KoolinwithKrauss In today's video, I returned to a mobile home where I had diagnosed a leaking and dirty evaporator coil. In the video I show step-by-step how to replace the coil Brazo the copper pull the vacuum replace the dryer the whole process. And then I walk you through charging it up... sorta. I hope you enjoy.
Today we are at, you'll forgive me if that's a little shaky, we are at a mobile home where I
recently, a couple months ago, gave them an estimate to replace the evaporator coil.
There you'll see what I'm seeing right there. Hmm, that ain't good. That was not like that last
time I was here. I think it has gotten wet. So come with me, we're about to replace this
evaporator coil and at least tell them about this so I can come back with some foam board and seal
it up. Here we go. It's been so long since I diagnosed this thing. I don't remember if we
need to do a cleaning out here. If we do, at least there's a water hose right there. That's nice.
Yeah, I would say it needs a cleaning out here. All right, let's get ready to pump this down.
It's going to be fairly easy. First, I'm going to go ahead and close this one off
completely before I even get started. And this one, it's going to take a little bit longer,
but I'm going to close it off and I'll bring you right back. I'm going to open it back up.
Okay, that is now open just a few turns. It is almost closed off. What y'all see me doing
is what we call pumping down. This compressor doesn't just compress refrigerant, it pumps it
and it comes out through this line and comes back through this one. So when I close this one off,
the refrigerant can't escape, but it can come back in. It's still sucking refrigerant.
So it pulls everything it can and it piles up behind this valve in the condenser.
That way we save our refrigerant. We call it pumping down. And right here, I'm going to
hold on a sec. Let me get my, where I can read pressures. Get this up and going. That way I know
when I have a good. I'm going to set this right here. I'm watching my pressure. I'm at about 100
PSI going low, going lower at 50. We've made it inside. Let me see if I can get a little light.
We're about to see just how much refrigerant was left in the system.
Shouldn't be much. That was tight. Now you see that there wasn't much refrigerant left.
That's a piston. Right now I'm going to keep as much of this 3.8 as I can. I'm probably going to
cut this right there. Kind of gives me options when I'm, it gives me options when I'm reinstalling.
The more copper I have, the better off I am. Now I just got to get that PVC loose and we can
pull this coal out. We're going to get a vacuum so that I don't make a mess.
That ought to help a little bit. Cut this using this right here to cut.
I think the drain is backed up. Created a problem for myself. This line may be in my way.
This one I can move out of the way.
But that, this copper right here, I have to make a couple joints.
Y'all forgive me, but I am hungry. You'll hear my stomach growling because I need some vittles.
Now I'll be able to get that out a lot easier. This thing happened to have been leaking.
It definitely would have needed cleaning. Let's get ready for the new coal. Actually,
the coal that I have, I don't think it's being produced anymore. And this is the last one I have.
That's an R410 multi-tonnage Mortex mobile home coal. And for some reason I can't seem to buy
those anymore. I think other companies are making something to replace this,
but I don't know why they quit producing them. I wish they still would. I think Aspen is creating
a multi-tonnage coil where you can replace the TXV. I'm pretty sure I have one in the shop,
but it's not the proper size for this. It's like a two and a half and not multi-tonnage.
But this one is specifically mobile home to three and a half ton, I think.
And to be sure, this is R410. And this is something I was trying to prepare for.
I went looking for some reducer couplings because this is seven eights and what we're
hooking up is going to be three quarter. Eh, it'll work out. Let's go put it in.
Y'all forgive me. I was having a little trouble getting my...
Okay. As you see, I'm going to have a slight problem with this right here.
That's what I need to be able to hook up the drain. Let's go ahead and cut this.
I do know that it should be charged with nitrogen. Maybe that's not the best spot.
Y'all forgive me. I'm going to have to go get a fan. It's kind of warm right now.
And the shirt I'm wearing is not particularly breathable.
Like I said, that is nitrogen. No need to get bent out in shape about it.
That is not refrigerant. Okay. I actually went by one of my stores today to see if I could find
the seven eights, the three quarter reducer, just so I could press the whole job.
And I'm not going to be able to, because I'm going to have to put my three quarters in there
and solder it up as well as this. I'm going to have to solder that. I'll tell you what,
why don't we go ahead and connect the drain, get that going. And because it can be harder to
connect when all of this stuff is in the way. So go ahead and do it, get it out of the way.
And then we're going to start working on this. I need to hook up nitrogen and everything. I got
plenty to do. Almost got it on. That is some nasty looking glue. That's done. Now I can
get nitrogen hooked up and I can start working on the rest of this.
You got to cut the end off of this one too. At least one revolution. Turn this the other way.
This, I'm actually going to swage it. Close off this glue.
Actually going to swage it, which means I need to cut that about right there. I'm going to be
swaging that piece right there too. And run me a piece of copper. I'm not going to try to
straighten that out. At least not very much. I'm going to make my bend right here.
All right, let me go get my supplies. We'll get all this kind of pieced together
and we'll start nitrogen outside. Let's see which one I have here.
Y'all forgive me, but I can smell that glue. It's pretty strong. All right, what I'm looking for is
this. This is the three-eighths head. It's going to go right there. I'm going to show
y'all how to set this up. This is a Yellowjacket tubing expander 60407. I'm going to show y'all
how to set it up so that it works every time. You don't over expand. Get that started.
Close it completely and then tighten this up. All right, now if you notice when I open this,
I can tighten that some more. But you just tighten it
with it closed and that is the proper depth.
I'm just going to the very tip of it expand that. There we go. Slowly. All right, I'm all the way
down. Turn this and do it again so that y'all can see. They'll stop wiggling. That one's ready.
Now we need to do this one. This is three-quarter and that is seven-eighths.
Let me see if this one is already bent a little bit. I'm going to bend this side a little bit
right here. This has a wing nut that I seem to have lost. Okay, I think we are ready to start
soldering. Let me try to find that wing nut. Okay, I got everything hooked up already. Open
this. Open this. All right, we are going to make sure this is open. Crack open that valve.
Make sure that's turned off. Open this. I don't want to do the full test pressure because
I'm going to blow my joints apart in there. Right now I have it on purge so I'm getting
if there's anything left in the system getting it out. All right, leave that on braze. These
on Schrader cores are already removed so the refrigerant can flow through and come out here.
Did I say refrigerant? Nitrogen. Checking my pressures on my tanks. Looks like I've got decent
pressure. Okay, I'm going to start with this connection right here first. I know that's
going to be hard to see. All right, y'all got a bird's eye view. I hope I don't set off that
smoke detector that we heard beeping a little while ago. At least add a little oxygen. It's
less likely to smoke. All right, I think this is done. I'm just going to try to make it look a
little better. Broken mirror here somewhere. How about this? This is one that's not broken.
All right, that solder goes all the way around. My next one is this joint right here
which is my only upside down joint. I'm going to bring some more heat with this one.
Now we're going to see. Did a decent job. Every time I touch something that's even slightly warm
I'm afraid I'm burning myself. So y'all see me jump. I'm not necessarily burning myself.
Okay, next one is not upside down. Let's see how we did. I think it's time to go do the dryer.
Y'all are going to see me install a bi-flow dryer even though this is not a heat pump.
More than half of what I work on is heat pump. If I have to put a dryer in something
I just stock the bi-flows. Too many times I have gone to install a dryer on a heat pump
and pick up the wrong dryer. And so a straight cool dryer will not work on a heat pump but a
heat pump dryer will work on a straight cool. So that's what I buy. There we go.
I haven't measured this yet so I don't know. Man that's awfully big. Is that half inch?
That says three-eighths. Y'all see that? That's kind of, that's a little bit loose.
Clean that up a little bit more. Technically you're supposed to cut out your dryers.
I don't always do that. Let's get nitrogen back on braze. I started with about
half a piece of solder. I think I'm gonna make that one little piece of solder last the whole
job. I always turn off my gas if I'm moving my tanks. There was one time I had my tanks in my
truck before I got, I was actually, I had an employee in a service van and I was working out
of my truck and I opened my door and I could smell acetylene. It's a dangerous moment.
My acetylene tank had emptied into my van or my truck and mixed with the air. It could have been
explosive. Looks good and that looks good. We're gonna turn this on. Hold on just a second. I got
to hook up my my other side here. There are no schraders in. Open, open, open. So we should be
building pressure. I'm gonna let this get up above 200 and we're gonna start doing a bubble
search. We are at 243 psi. I just pushed the test tightness button. Trying to let that settle out
for a little bit. Okay, timer has started. We're gonna watch this as we do a bubble search. Let's
go inside. My sprayer creates bubbles. I just don't want my joint. Y'all hold on just a second.
I don't want my joint creating bubbles. Now this is just nitrogen before I mixed up and said
refrigerant but this is nitrogen. These do not have schraders in them because of the difficulty
of this right here and trying to put a schrader in after you pull a vacuum. I'm gonna go ahead
and put the schraders in and I'm gonna pull through my manifold and while that's happening
we can clean this coil. I'm gonna go ahead and put in my schraders. Like I said, we're gonna
change them. I do not use them. Once I pull schraders out, I do not use them. I always
replace them. There's the other one. We got dryer still a little bit warm. You can actually see that.
All right, schraders are in. Just about everything ready. Open, open, closed.
All right, we should be in a going into a deeper vacuum soon.
It looks like we're getting steadily below 700 microns. Let it pull for a little bit longer.
I am really close to 500 microns. Some of what you're seeing here may be oil trapped
refrigerant that is bubbling off once in a while. That's why you see it fluctuating so much
but the closer I get to 500, the less likely that's going to be happening.
Almost there. Okay, we have arrived at that moment. I'm going to turn off
the vacuum. See that as clear as I can. 290 over 127. I've got basically zero sub-cooling
and 4.2 degrees super heat. All this hooked up. This little spot right here is what I was talking
about. I have sealed those off before and honestly it did me very little good. I've even taken this
out and flattened this piece to mount it but right now this one's ready to go. My bulb is
mounted. Everything's ready. Okay, so what I'm going to do is I'm going to quote replacing this
piece of ArmorFlex and getting me some foam for that return and sealing up that return.
Some foam board. All right, let's see if that affected our pressures,
our super heat or sub-cooling any. It actually made a huge difference. If y'all can see my
super heat is at 18.5. That is too high. Sub-cooling is too low. Now these numbers
are making a little more sense so I'm going to charge this with a little bit and see if I can
get my sub-cooling up without dropping my super heat too low. When I'm reading this, I'm reading
all these numbers. My head pressure, my suction, sub-cooling, super heat,
condensing temperature, evaporation temperature. All of it is important. My suction line temperature
is a little below 60 degrees. That is fantastic. My sub-cooling though is still
not where it should be which means I'm not getting a full column of liquid.
So mainly I'm watching my sub-cooling because we have a TXV and I'm paying attention to the
super heat while I'm watching these pressures. I don't want that to get too high because it's not
that hot out here. It's not but about 80 degrees and it's like 73 inside. 16 degrees super heat
is not bad but that sub-cooling to me is still a little bit low. It's real easy to overcharge.
That's why you see me doing just a little bit at a time. Super heat's come down a little bit
which means this suction line temperature is dropping. Sub-cooling still is not where I want
it. I'm at zero degrees. This is straight cool so it's not as charge critical as a heat pump.
My suction line temperature is now at about 55 degrees. Super heat's at 14 degrees.
Sub-cooling is staying right at zero. I see my super heat starting to drop. It's down to eight
degrees. Five. That to me indicates that no matter my sub-cooling is still hovering around zero.
I need to be very careful about adding refrigerant because
my super heat with just a little bit right now can go to zero. It's going back up to 10 now.
And my sub-cooling has gone up to 2.2. So I'm really close to where I need to be.
I would really like to see that sub-cooling around 10 degrees. I do realize that's not going to
happen. My super heat's sticking around 10 degrees so I'm going to leave it right there.
Well guys I do hope you enjoyed the video. If you did how about like and subscribe.