How to make a starter for a motor In this video we are going to learn how to make a motor Starter in which there will be one motor which is going to be operated for 2 different time, watch the complete video to learn more about in details.
Friends, just a few days ago the owner of a company
contacted me and
after contacting he told me that he
has a motor and to start and stop that motor
he has to make a starter.
Some logic will also be used to make it.
See, first of all he told me
that the motor has to be run according to two times,
meaning that if he wants, he
can make the motor run for 5 minutes also
and if he wants, So the same motor
can be run for 10 minutes also, meaning that there
will be only one starter, through the same starter the motor has to be
run for 10 minutes or for 5 minutes. Now they had to get a starter made for this motor
and get it made. When
they contacted me for this,
I made the complete circuit according to their requirement.
How to make the circuit, let me
tell you, this is the complete logic. According to this
logic, if we have to switch
on and off this motor. So for this we will have to
use all these electrical devices,
I have made the symbol of all these electrical devices
here, here I have a
contactor, here I have an overall relay and
this has become the symbol of the motor.
To operate the motor, I have made a three-phase
power supply connection here. Now, if
we turn on the contractor, the motor will start
and when we turn off the contractor, the motor will
stop. So if If we have to switch a motor
on and off, then to switch it on and off, we have to provide
power supply to the coil of conductor, so to
provide the power supply, I will
use this l3 power supply here. Taking the
power supply of l3,
first of all I will connect it with the terminal number 95 of the overall relay,
as you can see here, this is the
overall relay, here it has the terminal number 95,
here it has the terminal number 96. The
terminal number 95 and 96 of the overall relay is of
NC contact and
we use NC contact
for the protection of the motor, meaning that if
we have to stop the motor, then for that we put an
overall delay here. If we use NC contact,
then we have
connected the incoming power supply on terminal number 95. Now we have to
take a wire from terminal number 96
and which is our stop push button here. We have to
provide incoming power supply to it,
so how?
You will see here the
overall delay. From the terminal number 96,
a wire has been provided from there to provide
incoming power supply to the stop push button.
Now power will be supplied from the stop push button to the
start push button. And the
power supply from the start push button will go directly
to the A1 terminal of the coil of the contractor. Now
it needs neutral power supply. So for
neutral power supply, I
bring neutral power supply here and
through this I provide neutral power supply directly.
You
can see here that the neutral power supply has been
connected, now after making this connection,
if I turn on the power supply, after turning on,
if I press the start push
button, you will see that the motor has started
but as soon as I will release the start push button and the
motor will also stop. The
motor is getting stopped because the
power supply here has been cut. If we have to
keep the power supply on here, then
for this we have to press the start push button here.
Or if we
want, we can also make a holding circuit here,
so to make a holding circuit,
what we have to do is simply this
contractor, which will be the ano contact of this contractor,
like this
is the ano contact here, this one will start push button. We will
connect it in parallel,
how to make the connection in this way, let me explain to you a little bit
through the picture, so what
we did at the present time is that
above the contractor,
you will see that there is an anode contact like
this. You can see that there
is an anode contact here in this contactor, so this is the anode
contact, we will use this contact,
what we have to do to make the connection for the holding circuit, this is the
start push button, take
a wire from its incoming terminal. It has to be connected and
it has to be connected to this number 13 terminal.
Then what we have to do is that this is a
push button, we have to bring one wire from its output terminal
and bring it here and
connect it. It means that the
contractor's
We will have to connect both the anode contacts in parallel to this start push button.
How the connection has been done,
you can see here. You must have
understood so many things. Now the
circuit ahead of this should be connected in a good
way. So you understand, as it is
said in the logic that if
we have to start our motor for 5 minutes or 10
minutes, then for this we
will use two timers here, these
are the timers in this timer. I
set the time of 5 seconds on the current time and I set the
time of 10 seconds on this timer,
so after setting the time in both these timers,
what will I do that
this selector switch is one of the selector switches.
Point means that by bringing
a wire from the output terminal of the selector switch, I will provide
incoming power supply to one timer
and by bringing a wire from the other contact to that
contact, I will
provide incoming power supply to the other timer. This
means that If I keep the selector switch
on this position, then the power supply should flow from here
and through the flow,
power should be supplied to this timer.
Similarly, if I keep this selector switch
on this position, then in this condition the
power supply which The power supply that will come from here will
flow from here and go to this timer,
that is, it should go to the timer of 10 minutes.
Now, to
provide incoming power supply to this selector switch,
we will
connect the wire to the output terminal of the start push button. This means that the
power should be supplied to the timer only after starting the motor. For this,
I connected the wire to the output terminal of the start push button.
If I
connect this wire at this point or
connect it at this point. If I do this, then in this condition the
power supply will always go to the timer due to which
my motor will always
remain in off condition, so here we have a
timer, its function is that
after starting the motor, as soon as the time completes 5 minutes.
So if we stop the motor automatically then the
timing of the timer should
be counted only after we start the motor, that is
why I have provided the incoming power supply to the selector switch by
connecting air to the output terminal of the start push button.
Now to operate both these timers,
we have to provide neutral power
supply also, so
here I provide neutral power supply directly,
you can see here the
connection has been made, now here you
will see if I press the start push button. When I press the button,
my motor starts and at the same
time the countdown has started through this timer.
You will see that
after the countdown is complete, it has turned yellow here. At the
current time, you will see that the motor has
not stopped. The time of the timer is complete.
Even after starting the motor did not stop. If we have to
stop the motor, then for this we will have to use the NC contact of this timer. To
break the circuit,
this is the first timer
in which we have set a time of 5 seconds. We will bring the
NC contact of the timer that has been set
and connect this contact
with the power supply that is being supplied from here in the coil of the contractor,
meaning that
we will connect this wire to this wire. We will remove it from here
and after removing it, we will
connect the NC contact of this timer here.
Similarly, from its output terminal, we will
connect the power supply to the NC contact of the other timer,
then from here the power supply will be connected to our The
contact will come OK, so this is the
NC contact of timer one and this is the
NC contact of timer two. What is the NC contact of timer? Let
me
explain to you through a little picture as you
can see here which I have. There
is a timer here. The contact of this timer is
given here. Now in all these contacts you
will see that there is a terminal number 15,
here there is a terminal number 16 and here there is a terminal number 18. The
terminal number 15 is the one.
Common Terminal:
We provide the incoming power supply on the common terminal.
After this, terminal number 16
is NC contact
and terminal number 18 is ANO contact,
so for this timer we will
use NC contact, meaning that which is
our face. Supply is coming, bring that phase supply and
connect it with terminal number 15,
then take a wire from terminal number 16 and
connect it with terminal number 15 of this timer,
meaning that both these timers are NC.
We will connect the contacts in series.
Friends, if you want to become an electrician,
electrical technician or
electrical engineer, then
you should have such knowledge
that any machine you have can have a
starter and its wiring.
You can do its trouble shooting easily. If you
want to acquire such knowledge, then
join my course.
In that course,
I have explained in complete detail how
you can solve any problem. You will use electrical devices
like a push button,
I have told you how to use it, apart from this, I have told you
how to use a timer, I have also
told you in the course, along with that
in my course, I have also told you this. I have
explained
what is the reason behind using a device and
if that device is being connected somewhere
then why is it being connected at that place,
that too I have explained in complete detail. So
if you
want to get complete electrical knowledge then join my course for this. The
course fee is currently Rs 99 but at
present you can join the course for only Rs 3349
and The
validity of that course is life time, so if you
want to learn electrical wiring, then
join my course for this. You will get the link of the course
in the description.
You can join directly by clicking on it. Yes,
after making this connection, the starter which is our
starter is
completely ready. Once we
test it, then for testing,
I have turned on the power supply here.
After turning on the power supply, if When I
press the start push button, you
will see that the motor has started and at the same
time, the
countdown is going on through the timer here and as soon as the countdown is completed,
the motor stops here. Again
you see the start push button. Pressed, the
motor starts running, here the counting is
going on, as soon as the counting is completed,
my motor has stopped here, now if I want to make
this motor run only for 10 seconds,
then for this, this selector
switch is this selector switch. I will
select it at the number two position, that is, I will select it to provide
power supply to this timer.
Now here you will see that this
motor will run for 10 seconds. You
see here it will start. Pressed the button, the
motor starts and here the counting has
started. As soon as 10 seconds complete, the
motor will automatically stop.
You can see that the motor has automatically turned off,
then the timer can be run according to two different times.
Our entire connection has been completed. Friends, if you
make this type of starter and
if you want that our time does
not stop the motor, then for this you
will use a selector switch which has three positions.
Three position means that this type of starter.
Selector Switch: What will happen in this type of selector
switch? If we
select the position of one number here, then our five
second timer will work
and if we select the position of number two, the
timer of 10 seconds will work. If we
keep it in the off position, then
in this condition our motor will
run continuously until we
press the stop push button. Our
motor will run. Let me show you
this selector switch as well.
I will explain it from here.
After deleting, I provided power supply to this common terminal
from here, then what I do here is this
terminal number two,
from this the power supply went to this timer
and from this contact the power
supply to this
What will happen after making so many changes if the first timer goes off? If I
keep the selector switch here at O position, then in this condition after pressing the start push button,
you will see that there is no
power supply to any of these two timers.
Due to which
my motor will keep running continuously.
If I want to stop the motor, then I will have to
press the stop push button to stop it. The
motor will stop only after pressing it. Now
if I have to run this motor for a few seconds. If you want to get it
done, then I will select this selector switch on
a number position here
and after selecting it, I will press the start button,
then the countdown of the timer will
start here and
after the completion of the timer time, the motor will
stop automatically. Similarly, if I
select it at position number two,
then in this condition the motor will
run only for 10 seconds through the timer, after 10 seconds
it will automatically turn off,
so you can see here that the motor
is off. Friends, I hope
you liked this video. Friends,
if you want to learn electrical wiring in this way, then
join my course. At the time of joining the course,
this coupon code is new.
30 Please apply this so that the fee gets
reduced, so I hope you
like this video. If you
like the video then please like it and if you have
not yet subscribed to the channel then please
subscribe.