Digital Relays for Smart Grid Protection

IIT Roorkee July 201
61 followers
Dec 5, 2023
In this lecture, the functional block diagram of digital relays along with their performance indices are discussed.
[Music]
[Music]
[Applause]
[Music]
[Applause]
[Music]
good morning to all of you in this
lecture we will discuss about the basics
of the predictions part for the smart
grid system and discuss about that the
point that why we need protection and
what are the components of the
prediction system and what will do
the further classes as all of you know
that the power system is becoming more
and more complex due to the integration
of fax devices renewables and also we
have deregulation markets so due to this
the system is more complex and
protection system is also becoming more
and more challenging day by day but
however with the availability of good
computational facilities and advent
signal processing techniques and of
course we have very much dedicated
communication and computer
infrastructure so it is quite possible
to have very improved and advanced
protection schemes for the smart grid
system now the point is if you could see
that earlier our network from the
distribution side mostly was passive in
nature but due to the integration of her
enables like solar base technique or
solar best renewable system or wind
system or small hydro or we have fuel
cells batteries the network is now
becoming more and more active in
structure active in nature so as a
result the whatever technique production
schemes we have maintained for the
earlier system those techniques need a
very wide range of basically
recalculation or re arrangement or more
innovative structures or innovations are
necessary for the production part and
the smart grid system so keeping in this
particular mind so in this particular
curriculum or course we have kept also
the protection schemes for the smart
grid environment first we will discuss
about the basics of the protection
system mostly the digital relays will
concentrate
and after onwards will discuss about the
very first term that is islanding
release how this islanding release which
can help to island the system micro grid
system that also will discuss very
widely and extensively and then we'll go
for coordination of directional
overcurrent release where you'll see
that how this over current and
directional release the essential
components for the smart grid
environment where the as well as the
protection is concerned so coming to
this structure it is a very known
structure known layout for all of us but
you know the every corner of this
particular power network we need this
protection scheme without prediction the
system is basically not possible to
operate perfectly at 50 Hertz signal you
know that a five percent of the money
basically we dedicate for the protection
infrastructure of the system of the
power Network you can start from this
generation that is here the generation
we have this type of transformer and we
have the transmission corridor we have
the transmission infrastructure that is
basically 138 to 765 kV range and also
India is aiming for 1200 kV
infrastructure of the transmission
system next we have step-down
transformer and yes we have some
transmission system distribution system
and finally the consumers if you could
see the wide range of this power network
at every corner we have to basically
protect every element element by element
we have to protect it so that our system
will operate in a reliable mode in a
very accurate mode and we can supply the
quality things quality supplier to the
customers that is actually up here aim
and that is also aim of this smart grid
environment so where we should not get
any interrupt interruptible power the
power should not be interrupted to the
customers and the quality of the supply
that is a frequency and voltage should
be maintained at the particular level
and so without disturbing anything
the customer should be satisfied and
24/7 power supply should be maintained
with an efficient manner
the first manner and in a smart manner
so that is what this Smart Grid
protection schemes in and if you could
see that in every in cricket mass we
basically go for this Helmand we care we
go for pads so they are basically for
the protection of this body so similarly
for prediction of all the elements of
the smart grid system we need some
protection elements see this already we
have discussed that our system was
earlier if you could see this central
utility system it was just in a one go
or one flow Direction based powerful
system this was actually the central
generation and we have further the
customers the power flow was
unidirectional but now the scenario has
been changed that here if you could see
we have central generation we have like
fuel cell we have PV and also we have
battery and also we have wind so so many
renewable energy sources are now
integrating they penetrated to the
network and the small flow is now
becoming multi-directional it is not
anymore
unidirectional that is the first point
we have to be very careful so while
designing this protection schemes of the
system or network that is our first
motivation that if there is a key point
recicled is the main driving force that
it compels us that we have to develop
some new protection schemes or
algorithms or techniques otherwise the
system cannot operate at the 50 Hertz
this straight 50 Hertz signal we have to
maintain certain accurate protection
schemes and next if we could remember
our last blackout in India in 2012 July
30 31st that this whole northern Great
Eastern Great and not this great these
three grades are just disconnected from
the rest of the two grids that is what
it motivates us that this particular
blackout this is a very
disturbance a very large disturbance due
to this disturbance 620 millions people
affected this figure is not a small
figure and you know it had happened due
to the protection failure only one of
the digital relays that is known as
distance relay though it was due to the
load encroachment problem the foreign kV
line was tripped and after that other
lines are overloaded and finally the
disturbance propagated and this
particular system event is known as
cascading failure of the transmission
lights or lines so due to that the whole
grid not done grid then the Northeast
read an Eastern grid also to some extent
all are disconnected from the rest of
the two grids so due to this we have lot
of problems we faced in the last 2012
and many more
blackouts also had happened throughout
the globe India also so we are trying to
just check this kind of major
disturbances as quick as possible so
that we can save our economic and our
also we can save our society and also
our citizen that is what our main
motivation now if we keep all the
techniques very strong and efficient so
of course we can always check this kind
of major disturbances coming to the
topic what is at our relay as I said the
digital relay or electromechanical relay
or static relay you can say so these
relays at the heart of the protection
infrastructure so without relays there
is no question of protecting any
equipment that is what yes of course we
have many other protection devices like
fuse we have reclose but however release
the major components one of the major
components as well as the protection
infrastructure is concerned now if you
could see here we have electromechanical
relay we have static relays we have
digital relay now the question is why I
have gave to this three figures because
we have one evolution we started with
electromechanical relay again we use the
static type relay also now we are using
this
elderly the question is why this
evolution because we are moving towards
smart read we are moving towards a
compressed visualized network or society
or power network where we have to
basically make the components to speak
to each other to say as their data
information with each other so in that
platform this electromechanical relays
not any more capable of doing that and
where this digital relays possible with
help of this digital delay it is quite
possible that two relays or ten number
of relays or one hundred number of
relays can speak to each other they can
say at their data information with each
other or those relays can send the
voltage current frequency power whatever
the information we need at the central
label central control center of the
smart grid system that is also quite
possible if you could see that I have
just pointed out few points this easing
production facilities discontinued
components and parts and a shortage of
manufacturing and testing technicians so
these are the Party minutes of this
electromechanical based relays that is
where we are moving towards this digital
relay advantages I mean this PPT
emphasizes these are the advantages of
the digital delay and these are the
disadvantages also this points also
motivate us that why we are just
choosing this digital relay why not
electromechanical relay why not static
relay the first point is the cost of the
relay yes well I'll just address here
the cost of the digital relays more than
the electromechanical relay because we
are trying to minimize a customized
properly the different components of
this particular digital relay and we are
also trying to reduce this cost also as
this electronic gadgets are mostly used
inside the digital relay like analog to
digital converter the processor or
digital gorilla converters so different
types of electronic gadgets are involved
inside this particular
relate digital platform based relays so
we are trying to reduce this cost also
slowly the second one is this self
checking this relay has the capability
of self checking if any fault occurs
inside the circuit of this digital relay
it is possible quite possible to check
itself that yes at this point there is
some fault this really can take care it
is reliable and accurate because all the
flow of the power or the signals
basically control using the central
controller and also the flow data flow
basically are very quite reliable inside
the structure of the digital relay it
has also the function of auto reclusive
and this one is very important
functional flexibility multifunctional
flexibility here I just want to address
that suppose if I purchase one digital
relay that this particular relay will
work for me as an over current relay
directional relay distance relay
differential at fault release so we have
different types of release in our power
system those relays are basically used
to protect the different components like
transmission or distribution lines
transformers or some different type of
components so in that case what we do
basically single relay feet it will just
act as different types of functions so
it is a very like a gift for us like we
can will be happy with less cost we can
have multi functions so that particular
multifunctional facility is available
with the digital relay
we have also system integration system
integration is quite possible as we have
discussed from the digital delays but we
can always say at the data from one
substitution to other substitution one
area to other area that is what this
system integration and adoptive relaying
means another feature of this digital
relay where with the system parameter
change or with the system network
configuration change this really will
just adopt
accordingly to change the settings so
there
we can protect for any disturbance so
that we can protect the network for any
disturbance which is going to be in
separate in the circuit and also it has
this data storage there is a fault
locating diagnostic and these are the
features other features of this digital
relay where it has the capability of
detecting the fault
where the disturbance has occurred or
how to take proper remedies against this
particular it will also give the
pinpointed position of the disturbance
so that we can further maintain go for
the maintenance purpose so those are the
different features of this particular
digital relay and the space is also
matter basically we can reduce by proper
design of this electronic parts of which
are involved in a digital relay the
digital relay space can be also more
compact nowadays we are moving towards
the development of different advanced
technologies
so with that further also the space of
the station delay can be reduced and
this coming to the disadvantages of this
digital relay we have EMI and RFI effect
electromagnetic interference radio
frequency interference those
interferences are basically present in
digital relay and sort life with the
evolution of next generation or
processor you know as already we have
discussed the in digital relay we use
the electronic gadgets so if the
processor suppose Russ's or one or two I
am using so some version of the
processor if is coming with some
involvement or with technology
development so we have to basically rely
on the latest technology or latest best
technology best processor we have to
utilize in the digital relay that is
what this revolution of next generation
processor we have to replace the
technology with the recent or advanced
phase of the products these are the
subsystems of a digital relay if you
could see that we are just tapping this
voltage current signals from the
substation or switch head
the substation inside substation we have
measurement cities and pities this
city's provide the voltage signal and
cities provide the current signal so
there will just tap the voltage signal
and the current signal and this current
voltage signal signals will be fed to
the search filters search filter means
it will just remove any cells in high
frequency component which is present
within this voltage current signals the
search filters will help in removing
those high frequency components next
we'll go to the signal conditioning
States the signal conditioning block
helps in maintaining the signals at a
desired frequency level that is what a
signal conditioning block - basically we
have low frequency low-pass filters and
where we will just allow the desired
frequency that is 50 Hertz signal and
also we'll remove the high frequency
signals or undesired signal frequencies
I mean frequency components that is what
the signal conditioning block helps
after signal conditioning block it will
go to the ADC that is the NLF to digital
converter there basically we have one
sampling clock is ready to sample the
data at particular sampling frequency
what sampling frequency will maintain so
that the voltage scan signals are going
to be sampled at a particular time
interval so one kilohertz or two
kilohertz or full hours what sampling
frequency we are going to maintain this
ADC will help up to this we have the
signal analog and here the signal will
be converted from analog to digital
platform so this conversion is possible
using this ADC and the pro digital
converter after this conversion of this
analog signal to digital it will go
directly to the processor the processor
is basically the central unit of this
central block of this digital relay we
all the algorithms are executed if it is
basically an over current relay the over
current algorithm is going to be
executed inside the processor of this
digital really if it is basically a
distance relay or a multifunctional
relay so all the algorithms are just
written inside burnt inside this
processor so that whatever the options
and modes will just opt so accordingly
the output is going to be coming to our
system after this processor we have also
different parts like for this processor
we have RAM we have ROM pyram hosoi
pyram and mass memory after this the
digital output will go to another signal
conditioning states and from here we can
take it out for our external use you
know this digital relay provides the
digital signals and also analog signals
after this digital relay this digital
signal we can always convert this DD to
a digital to analog converter we have
also if you need this analog signal from
the analog D to a AC converter we can
take the analog signal and also we have
like a serial port parallel port to
communicate one relay with other relay
the two relays will speak to each other
but they can share their data with each
other using this communication facility
which is basically present inside the
digital really I'll discuss here three
points the first one is the RAM second
one is wrong and the third one is
theorem or a pyram what are the
functions of this memories of the
digital relay this is the internal view
of this digital relay where you could
see here this is the processor this is
our processor card and this three
sections we have shown the cities inside
the digital also we have cities it will
just scale down the current and it will
convert to the voltage and it will
supply to the IDC and from Medus it will
go to the processor all the calculations
and the based on the
voltage signals only even if we are
supplying the current to the digital
relay it will convert to the voltage
signal then it will be used inside the
processor now coming to this rampart
this Ram
it's is basically random access memory
it holds the input sample data as they
are brought in and processed basically
to say it's a kind of scratch pad here
it I have written here it will just
catch the signals it will just hold the
this particular digital signals then it
will allow to move further it will allow
to pass the signal to the processor
again after a certain time interval
previous data will be lost and new fresh
data will reach to the RAM and again to
process to the processor so basically
it's a it's a sketchpad which is
basically used during the relay
execution algorithm when the algorithm
is executed inside the relay so this
particular section memory section of the
digital relay will supply the data to
the processor for execution of the
algorithm and you it is random it is a
random Monsieur it is not permanent
memory now according to this ROM it's
basically the read-only memory this
read-only memory or programmable
read-only memory sometimes pyram will
also call it used to store the programs
permanently you know we are building
this programs or algorithms inside the
processor so those algorithms programs
are going to be stored permanently
inside the digital relay and that is
basically possible that particular an
illusion is possible is in the ROM
read-only memory the third one is appear
on that is the invisible from right it
is used for storing certain parameters
like the relay settings we'll discuss
about this what is the relay setting in
the worker and relay we said the current
value so what is the initial current
magnitude so that if any current exceeds
that particular setting value then the
relay is going to be small operator it
will just
to just give some trip command it's not
malapa it's going to give some trip
command if it is exceeds certain
threshold value or sitting with that
setting is basically present inside this
EPM that is what so these are some of
the memory sections of this digital
relay and also we have this we'll
discuss in this slide the CT different
type of city connections for the digital
relay this is suppose the main city this
is the power line where the current is
flowing through this particular line
poor conductor and this city is the you
know the in case of current ransomware
we have the primary as the power
conductor where the power is moving I
mean it's flowing from one direction to
other direction and this is our city
secondary we are expecting we are
scaling down the current to a lower
level which is going to be fade that is
generally right so this is actually the
main city and these are the registers
part a secondary side of the city and
from here we can tap the current values
to the release or we can also fade to
other meters other things or we have
also send this current data to other
computer miss trellis this is this type
of connection is known as the direct
connection directly the relay is
connected to the secondary side of the
city that is where the name is direct
connection of the main city secondary to
the digital really because we basically
the relay takes current and voltage from
the secondary side of the CT or PT then
the processor will execute the algorithm
and it will just provide some trip
signal that is what though M that is
what the nothing happens inside that is
still really now in the B section the B
figure if you could see here we have the
main city after that we have auxiliary
city directly here the digital relay is
not connected to the main city rather
the relay is connected to the genericity
secondary
here is the auxilary city this is the
primary and this is the secondary this
secondary is connected to the computer
relay sometimes this digital relay is
also known as computer relay or
numerically because it's basically if
you could see the digit this digital
Lily operations mostly it is related to
the computer how the computer operates
the same way the digital relay operates
this third one is we have this voltage
transformer connection this is our PT we
have primary section this is the primary
winding and this is our secondary
winding so different fuses we can take
it the secondary voltage we can take two
other relays or meters and also will
supply to by scaling down the voltage
further we can always supply to the
digital really this is basically the
potential divider section present
potential divider section we use because
the relay is basically it's a very
sensitive device it is an electronic
device so there we expect we should
scale down the voltage and current to
lower level so that the ADC card and the
processor card should not be affected
this is how this in Indian Standard we
have the city secondary current is
within one ampere and five amperes that
is what the Indian practice and if you
could see that nowadays the
manufacturers musical they manufacture
the city ratio in the range of like
fifties to five hundred is to five or
150 is to five or 200 is to five and so
on so by using this City ratios we can
always calculate I mean the current
corresponding primary current inside the
digital relay
similarly for PT the secondary voltage
we have 110 volt face to face right so
this is the input voltage this is the
primary of the this PT and this is
secondary side and here also we can
divide the voltages using the voltage
or this is potential divider and we can
supply less amount of voltage yes of
course that will be again multiplied
with the ratio inside the processor of
the digital relay to get the exact
voltage information right so now I will
come to multiple signal sampling
processes and this it's organization we
have now started with converting this
analog signal to digital platform and
you know the MUX is a basically an
electronic component which helps in
converting this carrying out this many
analog signal to many digital signal
many analog signal or many to one also
this MUX is a multiplexed input so these
are the analog inputs may be voltage
signal may be current signals will
supply to the input side of this MUX and
from MUX it will just go to the ADC
it's Ellis is basically the block where
this analog signal is going to be
converted to digital signal and of
course the sampling clock is necessary
as we have discussed earlier that the
sampling clock bug block this particular
block will provide this FS sampling
frequency at what rate we are going to
sample the voltage current signals that
is what the function of this sampling
clock block and also this is one feature
and further this is another architecture
where also we use sample and hold
circuit before passing to this MUX the
voltage current signals and after that
we just provide this different end of
digital converter for converting this
analog signal to digital and sometimes
also we do in this manner also this is
the third one separately DC for each
channel let us say I have three phase
voltages this is VA VB okay this VC all
are basically the analog signals and
also we have current signals i-80 and IB
T and I see if we have multiple channel
signals in that case also we can use
individual ADC individual it is an
electro distant converter
that is for this particular section and
using this buffer will supply to the
processor further action now here will
come that the sampling process as you
know in the digital relay platform the
sampling process is very very important
this is how this signal processing
techniques are nowadays are very strong
basically if you have to use this
digital delay so we have to make very
advanced signal processing technique
technique should be evolved quickly
celerity to just process the signals and
it will estimate the phases or frequency
for our use if the relay is basically
let us say based on the distance relay
so we have to calculate the distance of
the fault at what location the fault has
occurred the fault has accepted so if
our signal processing technique is not
that much of efficient signal processing
is not strong so obviously it will be
delayed in calculating these phases or
calculating the distance at the fault
that is very signal process signaling
sampling process is one of the major
part parts of the signal processing
technique sampling process if you just
take one signal at what sampling rate we
are going to sample the signal that
matters a lot we'll discuss about this
particular point that how the sampling
process affects the performance of
different training techniques or link
algorithms it will maintain at two
kilohertz what is going to happen if
I'll maintain my sampling frequency at
two kilohertz so what is going to be
result so that is what the impact or
effect of sampling process on digital
relay platform or digital relay
processor or algorithm execution you can
say let us say we have taken this sixty
and YT two signals and at certain time T
X and T Y how to calculate this theta
you know this theta is equal to Omega T
so if we have like at two different I
mean features of signals XT and YT for
complete their samples at instant T X
and T Y the references for the two
failures will differ from each other by
angle of theta so at time this TX what
is that failure angle phase angle of
this particular signal X and at ey what
are the phase angle difference between
two we can always subscribe and we can
calculate this angle difference between
two signals right so by this signal
processing technique it is quite
possible you can always compare that
from the reference point let us say this
is another signal so this is my
reference signal so what is the phase
difference between these two signals so
at this point what is the time and the
corresponding angle at this point of
time so what is the corresponding angle
theta to let us take the difference
between these two we can always
calculate the phase angle difference
between the two signals well it is
leading to the signal what is lagging to
the signal so of course we have take
some reference signal that is very very
important without reference it is not
possible to say that whether the signal
is leading or lagging that is important
a reference point is very important now
that is what the sampling I mean we have
taken this 50 Hertz signal see this is
here 0.02 one cycle ends here one cycle
starts from here one cycle ends here
next 0.04 a second cycle we open this a
third cycle you know pond you know it
forth and so on so if you take let us
say but one millisecond interval that is
basically FS is equal to 1 kilo Hertz
and your sampling time interval is equal
to 1 millisecond so of course will get
20 samples per cycle 20 samples that is
what someone here it will calculate
within this 0.02 exactly 20 samples we
are going to calculate and within this
0.04 we are going to calculate 40
samples so now the sampling rate is very
very important we should not exceed the
over sampling or under sampling the
sampling should be perfect as we have
discussed
during your p.m. you part of the
lectures that already I have discussed
what is and realizing effect sometimes
what happens in digital relays or in a
power network while sampling the signals
the fundamental signals should come to
the processor because we are interested
to calculate the fundamental frequency
component of the features like the phase
angle or magnitude of the fundamental
frequency signal and sometimes
intentionally also we calculate the
phase angle and magnitude of some
certain harmonic signals for our
application purpose but anyway if we
suppose sometimes what happens the
higher frequency signals behave as like
fundamental frequency signal or low
frequency signal so that kind of effect
is basically known as a lazing effect in
digital relay platform also we do that
we basically remove that aliasing effect
using the anti-aliasing filters that is
that comes under the signal conditioning
block and apart from that also we
maintain this Nyquist criteria that
during the something we have to maintain
the sampling frequency in such a manner
that the sampling frequency should be
two times greater than the higher
frequency component which is present
inside the signal so those are the
concept techniques are maintained while
designing the digital relay this is
another sampling rate you know if you go
for low sampling rate or higher sampling
rate so corresponding number of samples
per cycles basically cycling it will
reduce the number of samples per cycle
is going to be reduce are going to
reduce if you take let us say 2
kilohertz then the number of samples
will increase if we take 1 kilohertz the
number of samples per cycle 20 so
similarly if we just keep on increasing
or decreasing the sampling rate the
corresponding number of samples per
cycle will also reduce increase or
decrease now I will come to three major
terms which are used for the digital
relay platform we'll discuss and the
subsequent classes we'll discuss in
detail
the protection part of the smart grid
environment first we'll start with the
island invitation of the smart grid
environment then I will go for the
directional over-controlling practice
which are basically used for the
protection of the smart grid environment
now I'll come to this relay reliability
down you know the reliability term
itself defined as the redundancy it's
but can we achieve but I didn't see
duplicating the relying system and this
resonance can be costly proposition
another way to improve the reliability
to ask an existing release a protecting
an apparatus say to backup the
production of apparatus be this figure
can be also quantified like this the
percentage of reliability is equal to
the number of correct trips divided by
number of desired trips plus number of
incorrect trips suppose let us say we
have one power network and we have
different loads or enables are
integrated in the system and also we
have nodes and different buses and in
that case what will happen and how this
relay will trip at what conditions
should trip at what condition it should
not trip that that is physical decided
by this reliability property of the
digital relay and this reliability is
divided in two parts basically the
dependability and security of the
digital relay so we discuss about this
next slide this reliability two types
dependability and the security now
coming to this part this equation if you
could see what is this numerator thing
number of correct trips because we are
designing certain device this particular
digital relay it's a trip when it is
desired but it should not trip where it
is not desired but it is not intended to
do that that is what the meaning of this
particular reliability index now if
suppose I have just mounted here one
digital relay this digital LED are if
any fault occurs here in this section so
what will happen this line
it's now a faulty line but however if
I'll just denote a bus B bus C bus leave
us now this a bus bieber's this line a B
is basically handle a hilda night and
similarly this line C D is also one
healthy line the relation should not the
relays which are present at different
buses they should not respond for this
particular fault remember this is very
very important we should understand that
what is the meaning of this
dependability what is the meaning of the
security what is the meaning of this
reliability the relation should be so
reliable as the name suggests
reliability means it should be so
reliable it will just riff for what
purpose it is designed what it is
intended that is what this meaning of
this number of correct trips divided by
the number of desired trips plus the
number of incorrect trips right so the
desired trips plus the number of
incorrect rips total number of trips but
the relay will produce and that is what
the denominator part now I will come to
the dependability part this relay said
to be dependable if it trips when it is
expected to trip this is very important
see already we have discussed in this
particular figure that if some fault
will just occur the fault is going to be
incepted in line section this BC so
relay DRI is responsible to clear to
that particular folder however this let
us say this is r1 this is r2
this is r3 however at this point this r1
and r3 are not going to respond for this
particular fault f which is incepted in
line section BC that is what the meaning
of this dependability function or
dependability property of the digital
really now it is it's a trip if it is
expected to trip if any fault is within
this zone we'll discuss what is a zone
of the digital release if the fault is
within the defines own or area of this
particular relay then the relay is going
to respond that is what the
dependability and also we sometimes
quantify this figure that is the
swerd the dependability how the number
of correct trips divided with number of
desired trips so that is what is
dependability percent is now the third
one is the relay security the Requa
secret is that property of the relay
where the release basically designed not
to operate for any outside zone faults
suppose let us say some fault is let us
as I discussed in this figure the fault
is in Section B C now this relay r1 r3
should remain silent
these three these two relays out of
these relays to release should not
operate for the fault which is accepted
in section BC that is what the security
of this property of this total is only
this relay r2 is going to respond for
the fault which is accepted in section
BC that is what this security DOM and
how to quantify this the number of
correct trips divided by the total
number of trips that is what this
security is defined in figure so in this
particular class we have just started
the production aspect of the smart grid
course in this course that is our
introduction to smart read we are just
trying to have information some concepts
regarding the prediction infrastructure
and here we have discussed the basic
block diagram for the digital relay and
where we have discussed how this analog
signal flows and it comes to the
processor and further is goes out for
taking out giving some command to the
set breaker or also the stage anyway
also will communicate to other release
which are present in inside this network
of the smart grid environment and also
we have discussed the sampling rate and
how this particular sampling rate will
discuss in the further classes and thank
you
[Music]
[Applause]
you
[Music]
[Applause]
[Music]
[Music]