In stations with automation systems according to IEC 61850, network technologies are used for different types of information exchange. Binary information like switch positions or switching commands can be transmitted via the substation network. Analog voltage and current values can also be transmitted. From instrument transformers or sensors, the merging unit collects the measured values, merges these sampled values into a data stream belonging to one feeder, and publishes them to the substation network. The CPC 100 can test the ratio and polarity of instrument transformers in IEC 61850 applications.
In stations with automation systems according to IEC 61850, the standard for communication networks and systems for power utility automation, network technologies are used for different types of information exchange.
Binary information like switch positions or switching commands can be transmitted via the substation network.
Analog voltage and current values can also be transmitted.
From instrument transformers or sensors, a merging unit collects the measured values, merges these sampled values into a data stream belonging to one feeder, and publishes them to the substation network.
The CPC 100 can test the ratio and polarity of instrument transformers in IEC 61850 applications.
The CPC's high voltage and high current outputs are used to apply test voltage or inject test current on the primary side of the CT or VT.
The sampled value stream that is generated and published to the network by the merging unit is read back via the CPC's network interface and compared to the injected primary values.
When testing a feeder in a substation where other feeders are in operation, a number of sampled value streams will be present on the same network.
The CPC 100 injects a test signal with a characteristic waveform into the instrument transformer that needs to be tested, thus helping to identify its stream of sampled values.
This characteristic pattern allows the CPC 100 to identify the corresponding stream and channel automatically.
When injecting primary current as set by the user, the CPC evaluates the respective stream of sampled values and displays CT ratio and polarity, just as when testing a conventional CT.
The CPC 100 can help test instrument transformers used in IEC 61850 environments with maximum efficiency.