If you’re interested in more business related videos I’m starting to publish them for members. In time I plan on have a full selection on how to manage and complete every step of opening and running a business! Join this channel https://www.youtube.com/channel/UCiz21FXLOV65NTgiUfJsxTg/join
Hey guys, in the video I have for you today
I think it's going to be really interesting
Um, starts off with a blown low voltage fuse
which I take care of, I'll show you how I did
the troubleshooting on that one
and then I just check pressures while I'm there and there's a
problem, stay tuned, all right
Can you tell me what it's
been doing? It's um, so it's coming on
Coming on the, the, the...
thermostat here is coming on, if it comes on, but it blinks
and then it does not, it goes right out
Yeah, and the guy that came over, the electrician, he replaced
the uh what do you call those little
things, a low voltage fuse or something
and it went, it came on for a little while, then it
burnt it back out, I guess. Okay, let me see where
is your, actually I'm looking for where
for where your vents are, are they in the floor or?
They are in the ceiling.
Okay, so your furnace is up here? I think in here. Oh, let me see.
In this closet. Oh, there it is. I was looking for it.
I have no idea. Is that it? I think it's going to be in your attic.
I think it used to be in here. What is that?
Oh, that's duct work. Oh, ----. I don't know. All right.
So have you been trying to turn on the heat?
We did turn on the heat when the temperature first dropped just
to make sure and turn it back off.
And I don't think we've really paid attention to it since then.
Okay, I'm going to be going in and out up in your attic
and checking everything out, okay?
I appreciate it.
Okay, so it is a package unit and a heat pump.
All right, that makes my job a little bit easier.
It appears...
that she's describing
a low voltage fuse
that's blowing i think and
uh i see a fuse right down
in there it looks like it's blown so let's dig
into it okay we have a blown fuse and it looks
like they left an extra and i was trying
and trying and trying to find the fuse in here
and it goes right there if y'all can see
those two spade connectors i'll try to get
a little closer right here so the fuse is not even
in it right now that's okay i have a um
I have a three amp little breaker thing.
This right here.
A three amp little popper. I'm gonna
put that in place of the fuse
and see if we can diagnose what's making it pop. First let's put
this in where
the fuse goes.
I just heard
it click
in there.
Y'all hold on.
Right now I'm
just kind
of watching to see what happens.
Let's see if this fuse blows on its own. I don't know if I just caused
it to cycle off or what.
Anything could have caused
this thing to pop.
We don't know if it was running in heat
or cool so we have to check every wire.
I'm going to go ahead and get my meter out
and put on this because sometimes you can
pick up a high amp draw like five
or six amps before it pops your little popper.
I'm going to put
that right here.
Okay we are reading amps
and what I'm going to do
right now I'm going to jump from red to yellow that's the first one.
this has two amp settings one for 600
and one for 100 make sure you put that on the one for 100.
oh that was it i don't know if y'all
saw that but it went to 21 amps
just like that so what we need to do now
is think about what energizes when yellow
when it calls for cooling or heat it's a heat pump whenever the
um contactor receives a call
or the board receives a call for the contactor what gets energized
One is this board, the contactor,
probably some pressure switches,
but the first thing
I want to check is the contactor
because that is the most common thing and we can check
that by ohming it out.
When I talk about ohming out the contactor,
this is it hidden way up here.
This is one side of the coil where I'm touching right here
and this is the other side.
So all you have
to do is disconnect one side and ohme it.
I'm going to have to read you what the ohms say.
Just set your meter to ohm.
I can touch one side right here.
And I can't hardly see.
I'm not
reading
anything.
I'm getting open lead.
I'm
going
to try
this
again.
Alright, now I'm getting a reading.
Wow, are you kidding me?
Duh.
I want you all to be able to see this.
I'm going to try to show it.
And I'm getting a totally different reading now.
I'm getting 18.6 ohms.
That's not terrible.
But.
This right here, this wire right here
is probably what goes through my pressure switches.
This just notifies the board that a call is making it all
the way to the contactor so it can start a
timer for defrost.
This is the one I'm worried about.
Right now I just want
to check continuity
to ground. It's out of the way.
I have two ohms to ground.
So my pressure switches are shorted
somewhere. Let me see if I can find where they connect in here.
Disconnect them completely and let me take this off.
I'll be right back. Right now I'm following
these wires and that's both of them right there.
They're going to make another connection somewhere
so I'm looking for that connection. Same wire
because we're going to have more than one pressure
switch. This is leading
me over there.
Let's figure out
which one it is. I think
that's all the screws.
Here's one of
my switches
right here.
Where does
that go?
If y'all see
me I'm looking
at it.
All right I'm gonna have to cut all
that so I can trace it out.
All right my connections
are in here.
I just didn't see them. Let me go back over there.
Okay this blue is what comes from my board. You
can tell it goes in that direction.
So these are my pressure switches. I can bypass one
right now. Let's see if I can show you.
We're going to prove it's the pressure
switches if we can. I got to be
careful it's still hot in here.
I'm going to test this
which is my lead from my defrost board
to ground. i've got kilo ohms
and we're going to test this
to ground and what i
got i had mega ohms
on that one i'll shock
myself in a minute
i just got to
tell you what it says i got two mega ohms it's kind
of got me thinking i may have moved something
that was causing the short 3.8
mega ohms let's do a little search
and see if we can't find it
Right now, the way it is...
I'm going to hook it back up,
and we're going to try that same test.
I'm going to back you up a little bit with my 3-amp popper,
and I'm going
to jump from
red to yellow
again to
watch my amps.
All right, it just came on.
So whatever I did moving those wires,
I may have just moved it away
from whatever it was shorting,
so we need to look for it.
All right, some of those wires go up in here.
I might take this off.
All of this was bound up pretty good,
so I'm halfway thinking that's going to be okay.
i'm running out
of space
for my screws
and forgotten
what we're
going to see
under here
sometimes there's a piece
of metal that's why i didn't take
this out y'all see that it's been
rubbing right there there it is that's it right there
if y'all can see that little bit of metal
shining through okay can
y'all see that tiny little bit of shine right there i'll tell you
what i'm gonna take a picture of it with my phone
and see if i can have that to put in the video
But as you see, this one here...
Has been rubbed in too.
And that's my defrost.
sensor see if i can move that i have that taped up
but i think i'm gonna pull that through so
it's not tight if y'all see this that is still
touching copper back there and this is the switch
it goes to i got half of an idea here
but i kind of need to get i might be able to do it so
if y'all can see that that is what it ended up
like it's not perfect i can pull some of these wires
To help get them away from that.
That was one of them.
and there's a load of wires
that go up there there's there's
the one that shorted if y'all
can see these are my low voltage wires right here i got half
of mine to time again right there
because as you see this one right here has
been so i got a little more work
the reason i use two zip
ties is because one zip
tie touches the copper
and the other one
with the wires does not kind
of helps keep them separated
trying to prevent another
problem and if you remember this right here was rubbing
so i'm gonna re-affix this in this
position tighter
as you see this is that's
kind of loose you can
probably buy like
a double-sided
zip tie but i
have learned
to do this turn
that just
a little bit
no i'm gonna
pull it away
oh now i got it
really tight don't
turn that so it's not
so tight i think
that one is okay now
Okay, that one is not rubbing up against anything.
There is a spot down here.
I'm gonna go ahead and tie it to that one too.
So I'm not just fixing the problem I found.
I'm trying to prevent it
from happening again.
Sometimes during a really good startup,
a startup technician
can find stuff like that.
I
think
we're
good
to go.
Just me screwing in to these holes where the coil is
makes me a little nervous.
I'm going to get this put back together for you.
I don't like these loose ends like this right here.
Cover
on
this.
I'm going to put
that fuse in.
Take out my little breaker thing and put in a fuse.
We're going to
see how it does.
Alright, the electrician they called out here the first time
was nice enough to leave me a fuse.
Okay, so we have a 3-amp fuse in there.
Hold on a second, I've got to turn the power back on.
You'll know it's a fuse.
Okay,
the fuse
has not
blown.
But what was blowing it before was...
Jumping from red, I've got to be careful
because it's easy to short circuit it right there, to yellow.
I just touched it to the side.
I've got to show you something.
These fuses are cool.
Look at this.
It's got a little light on it.
I kind of like that.
What I was showing you, I accidentally touched it right here.
That's what blew the fuse.
Man, that's pretty nice.
It's got a little light on it like that.
I've got some more right here.
I'm just going to go ahead and cover these.
Man, I like that light.
That little fuse with a light, that's pretty cool.
I didn't know they made them like that.
Alright, those are covered and put back in place.
New fuse.
That was a Bussmann Easy ID.
I kind of like those.
So now we just need to go in and turn it on.
Sometimes we can be thankful when there's nobody home.
I'll show you.
If that was fully habitated, man, that would be nasty.
I am pretty sure that the electrician they
sent out here probably could have found that.
But...
They do what I do sometimes, it's the air conditioner,
he identified it as that, and he left it alone,
and that's just staying in his lane, sometimes I stay in my lane,
so there was actually a problem with that in Georgia,
the Conditioned Air Association, I forget what it is,
they were upset because electricians were changing motors
and stuff on air conditioners.
And the electricians were upset
because the air conditioning guys were running their own power wire.
And our ACC,
Air Conditioning Contractors Association,
lobbied so that we can do all the electrical work from the panel
to the air conditioner, including the disconnect.
So we can do that,
but I do respect the electrician for leaving a little work for me.
That's just how it works sometimes.
Do y'all see that?
A lot of movement.
Right now we're
running in heat.
a lot of
movement
and it
doesn't
sound
very
good
does it?
I'm sure
that is.
I gotta
look
at the
evaporator. That was some really high pressure.
I said that I needed to look at the evaporator.
We call what's in here the evaporator most times
but when it's a heat pump and it's running in heat
that's actually the condenser.
But we still call it the evaporator.
At least around here most of the time that's what it is.
Even in the dead of winter
Winner.
we're going to be running
the air conditioner.
All right that's clean.
I just checked the filter. The filter's clean too.
I'm going to leave
this off, plug it back up,
and check again.
At least I thought I was.
I think I'm in some kind of time delay on this board.
The board thinks one of those switches opened up.
I didn't blow a fuse, did I?
I don't think I did.
Hoo, hoo, hoo.
Yeah, I think I caused it to go into some kind of time delay.
That fuse is good.
I just need it to fire back up. That's it.
Okay, now I'm not sure if somebody changed the thermostat.
We're about to find out.
Oh, wow.
And by the time we get to that 32 hours.
It satisfied the thermostat.
I almost have.
I'm going to put that on cool.
Let's see if you want to add those as we get closer and closer.
That's off.
This is cool.
Amen.
Man, that thing increased like six degrees in a couple minutes.
That was fast.
Okay, come on.
Are you kidding me?
There we go.
Come on.
all right that pressure is kind of normal
for head pressure now understand we are running in
cool right
now it is it
was 79 degrees
in there now
y'all see i got
this open
i think
those pressures
are okay at least so
far what i'm checking
for right now
is a change when
i put
this on
for up
to 116
not bad
it does
look
like it
seems
to be
fluctuating
a lot
now that it's running in cool i'm going to disconnect my orange wire
and watch it again it is now running
in heat let's watch these pressures
ma'am not right now no ma'am
do you need to leave oh no i
was on the call i just finished look at my head pressure
head pressure is rising rapidly let's see
if that changes things
and maybe slowed
it down but it's
still going up
isn't it it's still
way too high
poor lady's
in there working
and i'm running the heat
yeah that's too high
that's going up quick
And you can hear it.
When it starts getting close to 500,
that to me, I feel uncomfortable with it.
Yeah.
See if that comes down
a little bit.
Not much.
This should be smoking hot.
It is.
Yeah, there's
something
wrong.
Y'all saw
that we
don't have
any TXVs.
We got two pistons in here.
That thing calmed down a lot when we put it in cool.
I'm trying to look and see if there's evidence
this thing has been worked on.
And the reason I say that, I'd like to know,
I'm beginning to question what kind of refrigerant,
if it's mixed or if it
has something in it.
There is one thing I think I can do.
What I have done is remove this.
That just seems terrible to me that it's shaking that much.
So this one, we're running in cool right now.
So that should
be cold.
Y'all see this?
I don't know if it was because I was running in,
ow, that is super hot.
No longer seems to be cold, maybe a little bit.
These are still cold.
I'm going to let it run for just a second.
That's cold.
These should not be cold.
This should be warm.
Y'all see this color difference?
This is this color difference right here.
I got it again over here.
All right, so refrigerant should be flowing this way into that.
And it's like it's cool.
It's cool right here.
That stripe goes all the way around.
Still
feels
cool.
I mean, to a certain degree, a little bit of that is normal.
We're supposed to be sub-cooling.
but it should still
be um like ambient
temp i'll show you
in fact let me know
okay that head
pressure is condensing
at 107 degrees what i'm going
to measure is my sub cooling i'm
going to go ahead
and put this on true
suction okay now we
can measure look
at that sub cooling
that is high like super high i told you
that felt cool
sub cooling should be around like i don't know 10
to 14 degrees 8 to 14 degrees something like that
i'm at 40. high sub cooling normally
means it is overcharged it's
the super heat the high super heat
means it's undercharged but high sub cooling
normally means it's overcharged but because i have
high super heat at the same time it's a little bit confusing
that super heat should also be somewhere
around 12 degrees.
Outside right now it's 71 degrees and that
pressure is a little bit high for me.
I got an idea what I need to do.
Y'all see how I let that just help it with all the shaking.
I figured I'd say to the end what I'm going
to recommend for this customer.
I kind of saw these same things when we switched from R22 to 410.
You would get high pressures in heat,
maybe low pressures in suction, so somebody's overcharged.
And what we're seeing is possibly a mixture of refrigerants
and not the correct refrigerant
in here. So it acts like that sometimes.
And to eliminate that I want to offer to replace
the refrigerant, go back with Virgin R410,
and then try to re-diagnose if it's still having a
problem. I hope you enjoyed the video.
If you did, how about liking and subscribing.
Check out the store in the corner. Y'all might like those little
Railer magnets y'all saw me using?
And I'll catch you on the next one.