Meter comparison Fieldpiece vs. Fluke

HVAC GUY
37 followers
Tools I Use In My Videos 👇👇👇
https://www.amazon.com/shop/hvacguy
Comparing speed, and accuracy of Fieldpiece and Fluke meters
#fieldpieceSC680
#fluke116
All right guys, I'm going to do a quick comparison
with the FieldPiece 680, the Fluke 902, and the Fluke 116.
Some of the criticisms we get about the FieldPiece is that it's slow,
but this one gives us options that these don't give us.
And I kind of feel like Fluke has not innovated
for the HVAC industry in a while.
So let's just see how slow this is and if it's
accurate compared to the Flukes.
Now this one is an unused 45.5.
Looks like it's been dented a little bit,
but let's see how it tests out.
And what I'm basically looking at is speed here.
That was pretty fast, 45.
Next we're
going to test
the 902, 44.9.
That was also fast.
And the 116, 45.
the speed problem that and sometimes i
do experience this with the fill piece but right
now it's not doing it you notice that's almost immediate
that's almost just as fast as these
another thing you might be worried about will you
trust it to ohm out a compressor how fast is the
ohm readings and how accurate are they well let's just look
at that this is a chrome bumper
little delay
there press
when i press
hard i get
a different
reading 0.16
0.2 ohms two
to four ohms
0.4 so actually the
field piece seems
to be more in line
with there is a delay
depending on how
hard i press
determines
the accuracy of the
reading zero ohms 0.01
and there is a little
bit of delay in reading resistance there
and as you can see this is direct and that 902 seems to
be all over
the place 313 38 4 2
10 so this one seems
to be less accurate
0.5 so in all honesty
i think it compares very well with the fluke 116
this 902 right now does not seem to be doing so
well so um yeah i would trust it to ohm out
a compressor there is a little bit of a time delay
on the resistance but it's accurate