A technician returns to a customer's home to troubleshoot a heat pump that is blowing cold air despite being set to heat. After inspecting the unit and adjusting the defrost timer, the technician identifies that the system was dropping to first-stage heat too early, which is insufficient in freezing weather. He resolves the issue by reprogramming the thermostat to keep multiple heat stages active until the set point is reached.
Guys, we have a call back here.
This customer where I was working the other day
and worked on her heat strips on this heat pump, she called back
and said it was cold last night and said it's cold in the house,
so let's go see what's going on. Stay tuned.
Knock, knock.
It got cold on you?
Yes, it did.
Let me see. You said it ran for several hours?
Alright, you know you turned it off, right?
It went off this morning.
All right, right now it's turned off to turn it on here.
You know this what is this for right here?
That right there that's setting all
the way over to the right is for emergency heat
That is just going to bring on your heat strips.
You want to put it on this middle right here
In fact, it's better if you just leave it alone
and adjust it with this up here with your temperatures
Whenever you need cool, you can switch it to the left.
But if all you're using is heat
mm-hmm just leave it right here
and adjust adjust it with the red thing right here yeah just adjust
your temperature up and down
as you want yeah I imagine 70 it's it's set on 79 that's what that
temperature is right there it's like I just put it on 78
and it's 72 in the room 72 in the room
it just kept going and going and didn't turn it off
and no heat I guess so was this in the middle
of the night when it seemed like it was blowing cold
and sometimes it goes cold like during the
day and it don't go off until we turn it off it
just keeps going and I hate to try to turn it off
You know, I want it to go off on its own.
Okay.
I'm going to go through and check things again
and make sure everything's working.
I'm just not sure what it's doing.
I might have to spend the night with you.
Anything going to go wrong with it?
That's
cold.
The coil looks fairly clean.
Let's open this up and look at our defrost control board
and see if there's an adjustment we can make on it.
All right,
we do have an
adjustment
right here.
it looks like it's on every 70 minutes
which means this can ice up and 10 minutes of running
and defrost may not be enough to thaw it out
so what you're going to see me do right here
is move that to 50
minutes and um there's
something else i want
to test we know that
it does go through
defrost now did i
do that by accident caused it
to do whatever it's been doing
it sounded like
the contactor
just pulled
in and out let
me get my meter
real quick
all right i'm
checking yellow to common right here i do have
a call did i do something to make it lose a call
right now i'm tightening up these little wire nuts
these little things are tightening these gray
wire nuts
speed up
the timer
keep a
track of
something
right
here
in case i'm
checking
to
see if we lose a call and i got
my leads on yellow and common
coming from the thermostat
and basically I'm just
watching my meter here
to see if I lose what
is 25 volts
I
think
so
tightly
placed
right
around
there
I
can't
get to
that
I
cannot
easily get to that yellow just to pull
on it and see if it's snug it's snug
that yellow you see right here and right
here do not come from right here these
are my thermostat wires they come from over here
so I'm kind of waiting to see
if this changes and if it does it again like on its own on its own
because i may have caused it
and if i did my problem may be something intermittent
that is right in here somewhere
so i'm gonna watch this for a second
and i'll bring you back okay okay that's not wavering
not at all i'll tell you what i'm thinking hold
on just a sec get away from this noise okay um
it's been close to freezing last couple mornings enough
to put ice on my windshield
and these traditional single stage like 14 seer heat pumps like
this when it gets that cold they
don't produce much heat at all maybe a temperature difference
of like five or six degrees i'm talking
about very little and that feels cold
when it's cold outside so um what i'm thinking is that the
thermostat is getting close to set point
and it's turning off the heat strips and relying on the
first stage of heat which is the heat pump
and it is not warm so um that's what i think is happening
i'm gonna look and see if i can program
this thermostat to keep the second stage on until
it satisfies if not i have a thermostat that can
do that okay i'm going to show you what it's doing
it's been like five minutes
and i'm already up to 78 in here i don't know if you can see this but
right there oops i didn't mean to do it it was it was on stage one
so when it's on stage one
it's relying just on the heat pump
and that's what i thought it might be doing let me see if i can
program
that to not do that
all right let me
see i'm gonna try
to get me a manual
for this let me
see if there's
let me see if there's a model T7257
my T7257
manual all
right here we
go that's what
i'm looking
Press menu button, press take, set, and hold for three seconds.
Menu, take, set, and hold for three seconds, F1.
Filter change reminder, next step.
Room temperature calibration, next step.
compressor cycle rate, next step.
Cool swing, heat swing, heat set point limit.
This feature allows you to set a maximum or no cool set point limit.
I am going to change that.
Fahrenheit.
12 hour.
Previous step
is 12 hour.
Come on.
Here we go.
Next step.
Pro-recovery.
That is on. That's pro-recovery. Program options.
I'm not going to change anything. Heat pump. On.
Dual fuel auxiliary heat pump. Off. Pan operation.
Emergency heat stages. Okay. This feature controls
a number of pieces on the whole side previous
to here we go this feature controls the number
one satisfy this feature allows thermostat
to keep multiple stages of heat energized until set point
is satisfied you want that to be on that's what
we're changing all right so now stage one and
two will stay on until it satisfies the thermostat all right
so that's a really nice option on those
pro one thermostats i don't think i can
do that with the honeywells um i do not remember having
that option but um in the past the only way
before you could control that with a thermostat
the only way i was able to deal
with that was to use two relays to bring on the heat strips
one to bring on the heat strips when the yellow was energized
and one to turn it off when it was
in cooling but that meant the heat strips
were on anytime the heat was on and yes i had customers
that would pay me to do that but being able
to make sure the heat strips stay on until the
thermostat is satisfied they don't mean it stays
on all the time it means once it brings on second
stage heat is going to stay on until the thermostat is satisfied
and that's what that customer needed
i hope that fixes their problem thanks for watching guys
and i'll catch you on the next one