I Found The Real Breaker Problem - You Won't Believe It!

HVAC GUY
37 followers
Tools I Use 👇👇👇👇
https://www.amazon.com/shop/hvacguy
In this video I'm diagnosing exactly why a breaker was tripping on the condenser and giving an estimate to fix, when others would've likely replaced it.
#hvacguy #airconditioning #bluecollar #electrical #electrician @MilwaukeeTool @ACIQComfort @Kaiweets
00:00 Introduction
01:11 Starting Diagnosis
03:33 No Power
06:16 Checking Capacitor
10:33 Ohming Compressor
15:24 Insulation Tester
19:59 Letting The Smoke Out
24:54 Confirming Diagnosis
27:35 Estimate and Ending
AI Generated·May contain errors
hey guys in today's video what i've been wearing
this thing all day long and i just realized i got
a hole in the neck in today's video i'm going
to a condenser to diagnose why it wasn't running
and i'll go ahead and tell
you in the process
i'll let the smoke out
stay tuned knock knock
hey i've come to see about this air conditioning yeah uh what's it
been doing it's not coming on
outside okay all
right let me see
your thermostat
first system
on I'm gonna
turn it down
come on take
a look
in here no P
trap float
switch yes
I'm gonna go
check it outside real quick this guy just told me
the last summer they all fixed it put a capacitor
on it and told him that it wasn't the right one
but this is gonna make it work
no nice warning
you know y'all hear me say
um lovely one of my granddads instead
of cussing he would never cuss
he would say well i'll
be john brown look
at how that is mounted
i hear a buzzing see
if y'all can
hear it that um capacitor
is just kind of sitting
there i'm afraid to touch
anything i'll make it
move no power
let's just
do a real quick
check i'm gonna go
back to checking
for power while
there is no power let's
make sure that if i turn
this on that is on i'm
gonna show you something
that somebody did here which is perfectly fine
this wire right here that goes to your condenser
fan motor is normally mounted on the bottom
but that is on the side of the contactor that has no
shunt or there's no break in the line there
so you can pull it off the bottom and put it on the top
that contactor has clearly been replaced
these wires don't normally go in lugs they go they have
spade connectors on them i'm gonna go ahead
and pull this out
and check that capacitor he did say
that oh 35.5 let's
just check and see
if it's it it's still
reading 35.5 okay
we know blue goes to
herm i kind of think 35.5
is correct out here it's kind of easy
to tell if i can nope there ain't
gonna be no numbers off that compressor okay we have two here
that have four spades so you have
to look at it and see which one is C
and which one is herm put this over here on microfarads
35.5 and 4.9
brown goes to fan
this goes to herm
that's my start
for my compressor
and this one is
run before i do much of anything at this property
i now have to um give estimates before i do
anything i may have
the proper mount for that capacitor
if not i can put some plumbing strap
on it all these condensers out here
are basically the same let me
see I did not let me check again
instead of just checking for um whether
or not I have continuity whether it's beeping we're going
to check for ohms
to ground oh 13 14 megohms
16 17 megohms let's check
on the start winding
went to open lead let's
watch watch this for just
a second now nothing nothing
let's um let's try to
make sure we have power take my light in there
to the breaker box and see um if we can turn on
power see if we have a trip breaker a 40 at five
okay um thank you that is what i needed to know
they put on a 35.5 so you've helped them out
i'll get i'll make sure they get the right thing
thank you
so y'all heard it needs a 40
and 5 like i said right now i
have to give an estimate for
everything this thing did trip
a breaker now a 35 on a 40 should
not necessarily trip a breaker
it may cause a high amp draw what i'm about
to do right here is turn on inrush which tells me the
amp draw when it first comes on because it does like
a high amp draw initially and um it should
be something close to let me see lock rotor
amps compressor regular rla is 12.8 and rla
lock rotor amps is 58 your inrush might
be something close to that 58 unless this one's
going to trip a breaker oh i heard
something pop trip the breaker
again now let's get in there and
take
a look do
not have
power i
heard
what
sounded
like
a spark i'm
looking
in here
see if
i see
anything burnt i look
in and get some more light
and i look in here to see
if i see anything burnt
i do that so i can get
a good a good ground
on copper wire i try
not to touch
anything except
one of the leads let's
just go to straight
ohms nothing nothing
nothing okay
so it's not ohming
the ground next step is to ohm it winding to winding
and i'm going to show you something
um on these when you're ohming these winding
to winding like right now it'd be real hard to tell
which one is common start and run normally
if you have if you have a triangle it's left to right
common start run or if there's one on the top
and two on the bottom it's common start run and if it
looks like it's twisted to the left
or to the right it's normally twisted a little bit to the
right so let's look at this again so this one
this looks like these two should be on top this one
should be on bottom and it looks like it's twisted
to the right just a little bit so this should be
common this should be start and this should be run
and when you're probing these out let's go
through it and even if you're wrong on the common start
and run it doesn't really matter
when you're probing it out okay this is common
and start and i have kind of hard to keep my
leads on there i have about 1.8
so i'm going to read common to run
and i have about 1.54
so that means when I go from start to run I should have 2.3
so let's go to the other two
and leave out common
I've got 2.95 that's I'm
not gonna I'm not gonna
immediately condemn it for
that because um that's kind of odd normally if it's off it's under
and not over like that so I
think it may be internally shorted i'm gonna try something let's admit
that Cowie sent this to
me and i accepted
because i needed
a real megohmmeter megohmmeter
that little soup coat one i had i'm
sorry but that was just absolutely not dependable
um if y'all don't understand what i'm talking
about there is i might figure out
how to use this thing volts all
right we are hooking up to the
correct one we are this is like an insulation
tester one at a time i'm gonna start out with
common and what this does is it
tests between my common and this
ground i will hold one right here
to see if i'm actually getting anything to ground
and i probably am there's a better ground i can
one where i can use
a clip we'll see about
that i'll crank this up
to like 500 volts
60 megohms am i doing
that correct i'm sorry
this is the first time i've used
this thing
and it looks like we're pumping
out 520 volts dc and i'm reading
about 50 megohms okay we're
We're gonna go to 1,000 and now we
are reading 40 mega ohms
and it's 1,000 volts DC.
The lower the ohms, the closer the short is to ground,
if that makes any sense.
The lower the ohms, the worse.
Okay, those tests to me were kind of inconclusive,
so I'm going to just leave the compressor unhooked
and we're gonna see if it trips a breaker again.
That's kind of like old school way of doing it.
there's a reason I'm
not suspecting the breaker
not suspecting the breaker
because I heard that
arcing sound out here if I had heard something like
that inside of course I wasn't hearing it
under load in there so now when I plug in this disconnect
the fan should come on and there should
be no problem man
I'm just looking
at this right
here that is so
close to shorting
out I'll let the
smoke out okay the compressor
is unplugged that means
that compressor i told i told you
my results
were inconclusive it's that motor that's smoking
now how often do you see a condenser fan motor
trip the breaker it's kind
of not very common let's um make
sure we don't have power this is
pulled out and we're going to do something
different you see the reason i'm worried about
this shorting out that wire right there is 24 volts hot
from the thermostat that is 24 volt voltage
right there this side over here is common
which is normally grounded so if that grounds out that
it's either going to blow a fuse or blow
a transformer inside that's why i am right now
i know we need a new capacitor
and i now believe it has
our problem has nothing to do with that
compressor. I know I ain't got
no power but I'm still skittish
about touching this. That's one of
my wires. We have three wires
for our condenser fan motor.
I'm in the process of this is the my
common wire.
I'm in the process of taping off the ends
and the other one which I mentioned earlier
is right here.
Okay so all those
are taped off.
Let's plug
our compressor
back up. That
that um insulation tester
or megohmmeter has a lot
of functions on it
that i don't really need
and i went through the instructions just
a second ago they don't really
explain them very well okay
so this time fan motor is going to be disconnected
and like i said i have to submit an estimate for
everything fan
motor is connected
and compressor
is connected now
let's go back
in redo the breaker
and try this plug this up i am gonna look right here
and see if i see any shorts or anything
do not see any
compressor
should start
nothing
is shorted okay
that confirms
diagnosis of
condenser fan motor that one is kind of uncommon
for a condenser fan motor to trip a 30 amp breaker
i mean in most cases the wires just kind of burn up
and inside the motor that's what we check
that's why we use meters and that's why we diagnosed
because that could have easily been
diagnosed as a compressor if somebody had
not thoroughly checked it yeah i had to let the smoke
out to make sure but yeah that's what it
is condenser fan motor I'll tell you
why let's let's move all
of these up here kind of out
of the way for the time
being i'm gonna move
my hots. My 24 volts hots
from over here to over here.
That's my common.
This one is basically my
signal. If I'm not mistaken
this one goes to the board.
This is a 24 volt coil
so as long as you
get 24 volts across it doesn't matter
which side is your 24 volts coming
and which one is hot. So
I know I need a new capacitor. I need a 40 and 5.
In fact if I got a pin here somewhere I'm going
mark that i don't i need a 40 and
5 and i need a condenser fan
motor all right cap 5 that's not
what i'm looking
for 1100 rpm amps 0.75 says
horsepower 1 10th confirmed
at rpm 1100 0.75 amps
on something like that i do use a um quarter
horsepower that's rated at about 1.5 amps
i use a quarter horsepower for anything quarter horsepower
and under and it works out just fine
you just gotta make sure you got the right voltage rpm
and then it has sufficient amps so
condenser fan motor capacitor something to mount
the capacitor with and let's see if we get approval
i do hope you enjoyed the video as y'all can see behind me it
is the time of year to um start on
cutting the grass and you know something there is the guy
who cuts my grass right here he does a
great job i hope he's stopping
because man i need it check out the store in the corner um i'll try
to put that Keweis um insulation tester i always pronounce
this wrong megameter it's not
a megameter it's a megohmmeter
or something like that so um it was actually very helpful the soup
code that i mentioned in that thing it causes
false diagnosis anything below 20 megohms it
marks as bad i mean there's no real way to read it
at least on this one you can and you can refer
to like the Copeland app now they do have some information
on compressors where how many megohms
should trip a breaker that's not always accurate
but at least it's something that can give you some
reference i hope you enjoyed if you did how about like
and subscribe and i'll catch you on the next