In this video, I visited a commercial property where the tenant thought that he had ruined his air conditioner with dust. What I actually found was that it was low on refrigerant and that he needed to call the landlord in the process. I was playing how to diagnose if a system is low on refrigerant and I'll show you how to diagnose this using super heat and self cooling.
Hey guys in today's video a friend of mine asked me to check on a system
because he thought he had clogged up the coil with dust and thought he had messed it up.
That's not what I found but I'm going to take the opportunity to show you what to look for
if you think a system is low on refrigerant and how to tell if it is using super heat and sub cool.
Stay tuned. Hey guys we are here checking on wood at shop where I work. I'm going to show
you a couple things that I'm noticing. We have a sight glass if y'all can notice
that's supposed to be solid. You're not supposed to really see any movement when it's running
which means it that foamy look that you see in there is vapor and um we call that flashing
but this is very cold and sweating. I'm gonna check pressure super heat and sub cool.
Let's get these off. I'll tell you what I'm gonna use my true suction right here
and as you will see I have red and blue on here. We are gonna hook up the red one to what we call
our liquid line. Whether it's running in heat or cool this line should be a column of liquid
and the fact that I saw a little bit of um vapor flashing right here indicates to me that I do not
have a pure column of liquid. This is you can tell by this little pink sticker right here
that this is R410 and you see right there that is a low pressure for 410
25 degree saturation temperature. So what I'm going to do is I'm going to measure super heat
and sub cooling. This customer thought they had a problem and asked me to look at it.
I'm actually looking at it for a store that is here and then we're going to probably notify
the landlord if there's a problem. Okay sub cooling is at zero and super heat is at 47.
Both of these numbers should be somewhere between or around 8 to 14. See that negative or near zero
sub cooling that is another indication if the sight glass didn't tell you that I do not have
solid column of liquid. Basically what it means is this high pressure in the condenser is condensing
at 91 degrees which means if I have a sub cooling you see the actual temperature of the pipe is 91
degrees which means this liquid is not fully liquid. There's still some vapor in it that's
why I have a such small sub cooling and over here the vapor saturation that is what it is evaporating
at what temperature and this temperature up here is what temperature it I'm actually sensing right
here and because there's such a big difference we have a super heat of 48 degrees 47.9.
It is 74 degrees in there this temperature right here should be closer to 60 and it's not that
pressure there should be closer to 125 and it's not. All these things in combination tell me
that this system is low on refrigerant. Now for some of the newbies that may have been clear as
but basically if you have low temperature like low temp drop low pressures
low sub cooling all of those are indicators of possibly low refrigerant but there's one that's
going to be high and that's super heat. If your super heat is high and you got low sub cooling
together that to me is a really strong indicator that that thing's low on refrigerant. I hope that
helps if it does give me a thumbs up subscribe check out the store in that corner I think I
figured it out and I'll catch you on the next one.