In this video, I'm talking with the lead Tech Support guy over at ACIQ about how to convert their HD air handlers from 240 V to 120 V. He walks through every step of the process and we talk about hooking up heat strips I hope you find the video informative and I hope it helps you convert a 240 V air handler into 120 V. #hvac#hvacguy#airconditioning#airconditioner @ACIQComfort @BlueCollarWarrior @HVACRSurvival @KoolinwithKrauss @Onemanhvac @Jakeinabluecollar
Hey guys, the video I have for you today has actually been a couple months in the works.
I filmed it when I was in Ohio, Vandalia, Ohio with ACIQ and it's about the air handlers y'all
have seen me install. I actually love these air handlers. I think it's the AHD or something like
that because they are dual voltage. You can convert an air handler from 240 volts to 120 volts.
You don't have to rewire the house for heat strips. If you've got 120 volts in the closet
for a furnace, you can convert it to a heat pump using these air handlers and I'm going to show
you how we convert the air handler from 240 volts to 120. And y'all forgive me shooting this in
vertical. I'm doing it like this because somebody shot the video in vertical. So I hope you enjoy.
We're going to do two different things and one, I want you to show me how to convert
this air handler to 120 volts. Sounds good. And then I want, if it's fully communicating,
how to hook up the float switch. Sounds good. All right, step one for 120 volts.
Something I'd like to point out here is that if you look at our connections here,
we have the voltage being split into two different spots. Okay, the first one is going to be to our
circuit board. Our circuit board is powered by 240 volts. And that goes right up here from this.
Correct. And if you put in heat strips, it's going to have a plug for that.
Yeah. Yeah. What's going to happen though is what I, what you should do if you put in heat strips
is reuse this cable because what's going to happen is if you get rid of this cable,
I'll show you something. If you get rid of this cable and you do plug in heat strips,
what's going to happen is you're going to plug in your heat strips, right? And we're going to
plug it into our circuit board. And it's got this. That doesn't matter. That's okay. That's our,
that's our S. In this case, it won't make a difference. But what's going to happen is
if we power this block, we're going to get power to our circuit board,
but you know what doesn't have power anymore? Our blower motor. Yes. This is when we get the EHBA
code all the time. It's because people are abandoning this jumper that powers our blower
and they just are powering the circuit board. Now you need this cable.
This cable does not come with the power for the blower motor, which is right there.
Okay. And we're talking about converting to 120, right? Right now we're just talking about,
just hooking up heat strips in general. Correct. So if we're converting it to 120, that's fine.
But I just wanted to say you brought up the heat strips and where it plugs in it. I just
wanted to point out where they plug in it. Well, let's convert it to 120. That's fine.
Plug it back in. I also want to point out too, if you want to zoom in right here,
I'll get you a light. Hold on. If you look right here, these little tabs actually had a lock on
them. See that lock? Yep. You have to push that in like this. Yep. I see it. They lock into position.
So you push in like that. So don't just yank them off. Yeah. You can't just yank them off. You got
to push in. Oh, it's backwards. That's why. You got to push in on that lock and you'll hear it
again. So this plugs into our board, just like I was saying a second ago. It's one of the,
and then this goes into our motor. Now, if we're doing 120 volts, right? We hook up our one. Let
me unzoom real quick. Okay. We put in our 120 volts on L1, our neutral on L2. Does it matter
which one's which? I would prefer if we always use the red. If you look at the circuit board
itself, and I'll pull it out here. The circuit board is actually labeled. Yeah. You see it right
there. It's actually labeled L and N. So I'd like to keep it that way. I wouldn't, I don't,
I've not tried it because I don't want to smoke an air handler, but try to keep it that way. So
be sure, because in most residential stuff, black is hot. Correct. So is red though,
in residential. It is weird. Your red's going to be L1 if this is 120 volts. Correct.
Our neutral will be L2. That's going to be your hot and neutral is going to be on the black.
Correct. When in doubt, look at the board. That's what I always do when I'm trying to double check.
All right. So how do we convert this part? Now, this part, pretty easy. Just take that out.
Plug it in. Do it again. Okay. So it comes from the factory like this. So it comes set up for
230. That way, if you do send it 120, it won't hurt anything. But if you want to go to 120,
we take this out and we plug this in. And if you notice, we get this call a lot, the 230 goes
nowhere. Yeah. And that's by design. This adds in the jumper that's needed in the motor to make it
a 115 compatible motor. Oh, okay. That makes sense. Now, does this board auto sense what voltage
it's getting? Correct. The board will, but there's one final thing we're missing and that's this.
This comes in the accessory terminal. The board will auto sense it, but the transformer will not.
So what you do is you unplug this. All right. Do that again. That comes in the bag with the
air handler? Right there. Okay. Comes in the bag of the air handler. We take that out.
Take that out. I like to take the lock out. It's just a little locking piece.
And then on the back of this board here, we unplug this. Where was that now? It was hidden
back behind the board. You can come this way. Okay. So then we can remove the lock.
These locking pieces are there so they don't accidentally unplug in transit.
I don't want them popping out. Not very easy to get off though without a thing.
They are there to piss off. Yeah, absolutely. Me too. Yeah. All right. Got it off. We pulled this
off and then pull off this locking mechanism too. Right here. Okay. And you're on this,
this right here? This right here. We're going to pull that off. Okay. So are we replacing that?
Yep. We're going to replace it exactly. So then we plug that in and we plug that in.
Now be aware this little pen saver comes mounted on this from the factory. So it does come like
this. We get this call sometimes where people will say that this doesn't connect. This is a
pen saver. This is preventing those pens from getting bent in the little baggie. So this little
pen saver holds the pen straight. So you just take that off. Let's get rid of it. Okay. Is this
exactly the same for the Extreme Air Handler? The Extreme Air Handler does it all automatically.
You don't have to do anything. But this is the, which one is it? This is the AHD non-extreme
454B Unitary Air Handler. The ones y'all have seen me install recently. Correct. So now this
is 120 volts. Ready to go. Out the box. We're done. Now what'll happen if you send it 120 volts
and you don't do this modification? What's going to happen is you're going to get really low output
voltage. So we get a call where you're seeing 14 volts. You're seeing something low. Immediately
you know they didn't replace the transformer cap. And then like I said, the motor itself just won't
run. You may get an EHBA code or something like that. The voltage isn't high enough. But switching
this to that. Now we get that call a lot too about the motor plug. Why these are barrel fuses. I don't
know if you've ever opened one of these. But there are fuses inside of this. How many amp fuses is
that? They're 15 amp fuses. Now what it's actually here for though from my testing and what I have
found is it's here in case you switch this to 115 and you send 240 to that motor. It's going to give
you one more chance to get it right. Before you blow. Before you blow the motor. Before you straight
wire the fuses. Correct. Before you straight wire the fuses. Now let's say hypothetically you did
install those heat strips, right? Let's say you installed those heat strips and you did unplug
this motor, right? You mean coming back with 240 post 120. Yep. Now we're coming back 240. Yep.
We're hooking up all of this. We put in our heat strips and we do have power to our board. And
we're seeing that EHBA code and it's a new install. Most of the time that means that your blower
motor isn't getting power. So what do we do? We don't have the cable. We threw it in the trash.
The answer is if it's 240 we can remove these. Put terminals on them. Now obviously you can see
I cut them. I put these on here. This is not how it comes from the factory. And you can put them
on L1 and L2. This will power your blower motor in case you lost this wire. Okay. You don't
desperately need this wire. But it's important that you try to use the wire if you can. Something
I have seen. Yes. And I'm not going to say that I've actually done it. But we take these wires.
Yeah. And we put them here. I've seen that before too. And that's probably okay too. The only thing
I will tell you that I try to advise technicians on when I see that is just make sure your circuit
has enough capacity to do it. If it does it's fine. We can move that. We can even put them there.
We can do you know the 14 gauge jumper to do that. As long as your circuit. Let's say it's a 60 amp
and you only have a 5 kilowatt. You have plenty of capacity to put your own handler on. The majority
of the time I've got something that might have 15 kW. Yeah. But we're coming back with something
that can produce heat at low temperatures. Sure. I'm dropping the kilowatts. That's an acceptable
thing too. Because all this does is this powers our actual heat strips. Our relays are actually
powered by this plug. Yes. Which plugs into the front. So these relays will energize and turn on
and off. So what he's showing you is the low voltage hookup for that controls the electric
heat. Correct. So that goes to the relay. Goes right here and it's already hooked up to your.
But this not getting this power or not getting the power to this side is a reason why these
boards don't turn on. These boards are not powered by 24 volts. As a matter of fact you
can take the transformer out if you're doing full communication. Now you need it for like the relays
but the boards will turn on and activate and do everything they need to with high voltage. The
low voltage is for your transformer or for these relays or for a couple of other things. The boards
will turn on. So is there any reason for the transformer if you have no heat strips and it's
all communicating? I've tested it without that and I have not seen any issues. I have seen that the
24 volts like I said goes to this 24 volt relay and then it goes to your RNC. However DC communication
is what's powering this board. It runs on this communication block. And then of course we're
S1, S2 to the outdoor unit not using 24 volts. Also the outdoor unit is not powered by 24 volts
either. The outdoor unit circuit board is powered by 240. So have you measured voltage on this?
Can you tell somebody when you know it's communicating and when it's not? Short answer
no. Because let's say hypothetically we could right. I tell people this every so often. Let's
say hypothetically we could. Let's say we hooked up an oscilloscope and we were able to measure it
right. We don't have a reference to what those actually are. I'm talking about these communication
to the thermostat and the condenser. Yes I have not been able to reliably identify that. But what
I have done is anytime especially on a new install that we're having an EHBA error code or
an EL01 which is a communication to an outdoor unit. Anytime we're having that I usually always
attack the wire. The wire is usually what I'm trying to figure out right. So take both sides
take them off. O them out right. We should have nothing and then connect them and we should have
virtually nothing. I did this with a contractor the other day and for some reason with them
separated we were getting 40,000 ohms. I didn't know that that's why he was having a communication
issue but it's usually something that has to do with the wire itself. Okay the reason I ask is
sometimes with mini splits in the what you call it 14-4. Correct yeah. You can measure a varying
DC signal and at least give yourself the impression that they're communicating. Yes positive. So we
cannot do that here. No no because we don't also even know what it's supposed to be. What I would
hate to say is that yeah let's measure it and if you don't get positive DC voltage up to 17 we'll
then go ahead and condemn the board but that would be a lie because there are some that may do 20.
There are some that may do 12 right. There is no reference point for that. I have not been given
anything nor have I seen it. Now with many splits I do know that yes between like two and three you
should see like alternating positive or negative but I've never seen somebody be able to say oh
well it only went negative 54 DC volts and the I've seen it's 25 so this board is bad. I've never
seen somebody try to condemn it one way or the other. It's just a tool for troubleshooting. It is
and the only way to read and give you a good idea whether or not it may be trying to communicate.
Correct the only problem is which one is not communicating then right yeah that's where you
I'm gonna tell you I worked on some train communicating boards and if you have a
communication error you can unplug the communication wires and read the voltage on the board and if you
get a certain voltage like 16 volts yep it's good you plug up your communication wire it goes to 14
that's normal yep and that's one of the ways they troubleshoot the board is so it's a great question
so I don't want to say that you're helpless right I'm not going to say that what do we do the answer
is and I tell my Texas all the time change it to 24 volts let's actually use that wire and do
something that we know right so for example if for some reason you have it set on cooling with
ha and hb and s1 s2 outside and neither one of them are doing anything my first step I tell them
is all right we're done go to the air handler we're going to go ahead and set it up in 24 volts
right shut everything down turn on the sw1 dip switch we're going to jumper r to y we're going
to force this thing into cooling let's see how it responds now let's make sure we have the right
voltage and even in some applications what you'll see is the outdoor unit will actually start to
respond or if the outdoor unit doesn't respond I'll put that thing in 24 volts then we can try
to decipher what is our problem child right is our communication problem on the wire is it because
we're not getting 24 volts outside we get a break in your wire but we didn't do any wire testing
right so there are some things that we can do especially with the 24 volt options that we can
just jump it and force it to run in that regard which is what I like to personally do
I told you it was interesting so I really like those air handlers they are very versatile and
I've installed several of them and I hope to install some more soon
if you enjoy these videos please like and subscribe if you're out on a job trying to
figure out how to wire one of these up give me a thumbs up check out the store in the corner
I'll catch you on the next one