If you’re interested in more business related videos I’m starting to publish them for members. In time I plan on have a full selection on how to manage and complete every step of opening and running a business! Join this channel https://www.youtube.com/channel/UCiz21FXLOV65NTgiUfJsxTg/join
In today's video, I take advantage of having to check pressures on my own system at the shop to explain what superheat and subcooling or how we achieve those numbers and what they mean. In the process, I also described the refrigeration cycle because it is important to understand it to understand what superheat and cooling all I hope you enjoy the video.
Hey guys in today's video the whole purpose of this video is to address the question
about superheat and self-cooling. What they mean and why we use them to check pressures and verify
if something is properly charged. I'm going to try to go over it and explain it in layman's terms
as best as I can. Stay tuned. Air compressor running in the background. My shop is next to
an automotive shop. I'm going to be checking these with the field piece probes. I happen
to know that this particular system has a TXV on it. Okay in order to do superheat and sub-cooling
you got to have these these probes right here. Before I before I pull up the numbers on this
this is a heat pump so this can go in either direction but right now we are running in
cooling which means the refrigerant is leaving from this line
this line right here in the form of a liquid and it's going to a metering device and that
metering device kind of chokes it off and this side over here is creating suction so
on the other side of that metering device it has a lower pressure and the whole trick
sorry if the sun is the whole trick with refrigerant is when it starts to boil off
you reduce the pressure on it enough it absorbs heat it's kind of like spraying alcohol on your
skin and when it starts to evaporate it feels cold it is the same concept except we're doing
it in a controlled form using a liquid under pressure that allows us to do that over and over
and over and over again so I'm going to show you the refrigeration cycle this is something I used
some AI to create for you so you can see the visual and this line right here is my
liquid line inside it starts as a hot gas at the compressor and then the condenser
which is right now what this is the condenser cools it off so the compressor creates a hot gas
and then the condenser's job is to cool it off so it takes normal temperature air and blows it
out the top at a hotter temperature it's warmer coming out the top than it is going in the sides
so that refrigerant when it comes out the compressor is a hot gas
and the refrigerant is cooled by the condenser and it becomes a high pressure warm
liquid it condenses inside the condenser that's why we call it that so when it gets sent to the
metering device we want it to be in the form of a liquid that's why we call it the liquid line
and then it goes to the evaporator goes through the metering device and because it's on
because it's inside we're in the cooling mode that metering device creates a cold evaporator
which heats up the refrigerant again it boils off it turns into a vapor and gets really cold
so it absorbs heat and then comes back to the condenser in the form of a superheated gas
now i have gotten into the subject of sub cooling and superheat and what that means
so i'm going to pull up my application now and i'm going to show you the superheat and sub cooling
that i actually see on this piece of equipment right here and y'all can see here
i hope it's not the sun's not too bad
y'all can see here i have about zero degrees sub cooling and 19 degrees superheat
the reason that is important when i say we have a txv as our metering device inside
the txv controls the superheat so in normal conditions this superheat should be around
like 14 15 degrees but it's not and that sub cooling this is my superheat here the 18.8
and that sub cooling at 0.3 tells me that this system does not have enough refrigerant in it
we measure the sub cooling on a system that has a txv at the evaporator coil because that txv is
supposed to take care of the superheat for us it makes it fluctuate up and down depending on
temperature if you do not have a txv you probably have a piston sometimes there are capillary tubes
whatever it is is it is a fixed metering device there's also electronic expansion valves but i'm
talking about just basic residential systems normally have a txv and a piston we charge
pistons by superheat depending on the temperature inside because that superheat fluctuates and it
needs to be within a certain range so i'm going to talk about exactly what sub cooling and superheat
are all right this right here is coming out of the condenser as a liquid the hot gas gets cooled off
and it condenses into a liquid and right here we can see that that liquid is condensing at 107
degrees so every degree that this drops below 107 degrees that is sub cooled liquid and it
should be like between 8 and maybe 14 degrees below below that temperature of 106 degrees
now this one we measure superheat now i told you the evaporator absorbs heat it gets cold when the
liquid refrigerant is forced to expand and evaporate it absorbs heat it's a vapor you don't
want liquid coming back to your compressor so to ensure that you have pure vapor we measure
the temperature and once again it is evaporating at 44 degrees so every degree above 44 degrees
that we are sensing right here is superheat it is heated above that temperature so that tells me we
have we have 19 degrees superheat that is what superheat and sub cooling technically are a
difference between the temperature that you are reading and the temperature it is either condensing
or evaporating at i hope that was helpful i may have just made it clear as mud but that is super
heat and sub cooling why we check them and what it can tell us thanks for watching if you enjoyed
the video please like and subscribe and um check out the store in the corner the links in the
description and i'll catch you all in the next one