If you’re interested in more business related videos I’m starting to publish them for members. In time I plan on have a full selection on how to manage and complete every step of opening and running a business! Join this channel https://www.youtube.com/channel/UCiz21FXLOV65NTgiUfJsxTg/join
Hey guys, in the video I'm going to show for you this is a familiar place because
we were just there replacing a line set that was stolen and after that we found
that the evaporator coil was leaking so I replaced the evaporator coil and while we
when I finished replacing the evaporator coil while I was outside it blew a low voltage fuse
and I tried I didn't understand because it's running in cool the only thing that's energized
is green and yellow and I couldn't figure out why I was blowing a fuse so I'm gonna take you along
on this trip back it blew a fuse again when I was gone one of those um tail light guarantees
I fixed it and then that night it blew a fuse again so I'm gonna take you along on this trip
because I found out what it was doing and at the very end I'm gonna explain what was happening
guys I am investigating a low voltage short it keeps blowing a fuse here I am jumped
to red at least I thought it was I'm gonna jump I've got the thermostat turned off
I have green exposed over here apparently blower works I have the disconnect pulled
outside so we can jump to yellow blue every time I bring the um that is from outside that is my
white wire every time I bring on the it's like I walk away I can't figure out this is my like my
third time out I don't think it's my green wire it's like whatever is happening won't happen
long enough for me to find it and diagnose it all right right now we're gonna jump to
yellow if nothing else the fan should probably speed up that's something that we should hear
up here okay that seems to be doing okay let's take that off the yellow for right now
I'm gonna jump to the only others I have to jump to are my blue
for my reversing valve which I'd like to assume they're not using but um each time I put power
back to the thermostat I find it on heat all right the only one I have not jumped to
is my white I have it separated right there for a reason let me see if I can see if I can hear
this click I don't know if y'all can hear that but I can so that solenoid outside is
clicking anyway all right last one as y'all can see I don't exactly have the best place to sit
up here okay white going to my thermostat looks like gray that does not exactly uh-huh I see it
I see it right here uh is that brown I mean that that white almost looks green
could we be confused at the thermostat I think that might be the case
because that brown that we're using for common looks an awful lot like this this right here
uh-oh y'all see that the spark I don't okay that spark tells me that that connection
is why I'm blowing a fuse let me kill that real quick those are my two whites
I told you every time I put power back to that thermostat it would
show that the heat was on okay let's y'all see that we are still sparking
that is what's blowing my fuse all right this is my white on on my thermostat it looks more
like green that is not blowing anything and this is white outside not blowing anything
okay my low voltage short is in here at least now we know I couldn't figure it out because
I can't imagine someone running the heat right now okay I have little heat relays in here
kill this power so I think we have it narrowed down I just and that is not popping I'm afraid
this is a three amp breaker and um if y'all see that spark right there that's pulling
too many amps that is where that is where um my short is let me kill this real quick
okay I've just eliminated the low voltage to the heat strips that's basically what that is
so now if we do this again and look at that okay so it's not the board there's nothing outside
it is in here okay the controls on these are y'all see those are my low voltage wires right there
I only have one heat strip
I can't see what I'm doing I might be able to get that off with this right here
no I do have the right wrench in here I just gotta find it there we go I'm very thankful
because at least now we know what's this system was actually had the line set stolen and it had
been vacant for a while before they stole the line set okay I'm just gonna get a whole new
relay I could do that with a um with a sequencer I'm gonna go get a new relay that's what I'm gonna
do those relays are actually DC relays and um when you get the relay get the little DC converter
because it it rectifies the signal let me put this go ahead and turn that on so the thermostat
can be timing out put a cap on that until I get back over here all right now they can have some
air I just need to get their heat all right that should shut off everything it is this job's been
getting to me I kind of got the the low blood sugar shakes so I got me a little something to
eat while I was gone let's make sure we do not have power this does just have one heat strip
so that number 10 wire is big enough
and that poor ground is hanging on for dear life my buddy Jake would agree Jake Porter would agree
with me on that one I would like to think I could call him a buddy friend okay this I'm gonna I got
the I got the replacement part in my pocket but that right there is a rectifier it takes your AC
signal and converts it to DC and this in here is my oh my I just realized something I have two of
these it's double isolated and I don't know which one I only got one I'm not used to this thing
being double isolated like this y'all hold on y'all forgive me I have one on each side
let's see if there's a way I can tell which one is which one of them was shorting let's see if
measure the ohms on that one 543 ohms really let's measure the ohms on the other one
we're talking about the actual DC coil on these relays 546
okay there is no low voltage that goes to the heat strips
all right so I'm going to undo these right here and we're going to ohm out this rectifier
nine mega ohms is that right and here's the other one stay all right all right that's 1.6
kilo ohms all right I pulled a good one out my pocket or the one that I just bought anyway
and see if we can tell all right that's the good relay over there and these are the two rectifiers
this is the rectifier I just bought and it looks like eight mega ohms all right one of these was
outside of that range it was on kilo ohms all right now I'm at 200 ohms
eight mega ohms okay I'm gonna say this is my problem I'm certainly gonna
we're certainly gonna try to
replace that piece and see if that works for us
all right I gotta get power turn that off y'all give me just 40 I've got two four actually 246
I really don't want to blow another fuse even though I've got a bunch of them right now the
thermostat is in time delay so I'm gonna take advantage of that there's so much for time delay
we're gonna check out our heat strips again look at that I have no spark
wow that is wonderful that is great news all right take this out there we go y'all know what
this means I um I don't have to come back and if they turn on their heat in the middle of the night
or in the morning it is not going to blow that little fuse that is a thanks be to god moment
okay so these people were turning on the heat they didn't understand how to use their thermostat
I'm outside working on the cooling and they turn on the heat emergency heat at that and it
would blow the fuse that's why every time I would power the system back up it would be set
to emergency heat and I'm like is there something wrong with the thermostat there wasn't excuse me
they were turning on the heat now if they want to turn on the heat it's not going to blow that
little fuse that one is done that job I honestly feel like after all the work we put into it it
been better off just to change the thing out but the coal was under warranty so I don't know in the
long run it worked out the apartment next door the other side of the duplex we replaced the
line set on that one I'm waiting for somebody to actually move in and we're gonna go back and try
to pull a vacuum and start that one up when that happens I hope you enjoyed the video I have I'm
forgive me I got my little jarrito
I've been in my metal shop building a return box that I'm going to have to put together
in the wall because I'm increasing the size of the return and I'm probably going to do that tomorrow
so if we can get it done I'll sure have a video for you it'll be a good job because it's supposed
to rain all weekend that's gonna be mostly inside so looking forward to it if y'all like the video
please like and subscribe check out the store in the corner a lot of the stuff I use in my videos
is in the store and I gotta mention if you want to be an ACIQ dealer they have some fabulous
equipment in fact they've got one piece of equipment I'm probably going to get to install
in my house because I can run a mini split in my bedroom and a regular air handler in the attic
so we can keep the bedroom at a colder temperature and the it's just real nice because we like to
turn the temperature down real low at um at night and there's no sense in cooling down the whole
house if I can have a mini split head over over my bed saves us money so if y'all want to be a
ACIQ dealer there's a link in the description and I've been using Jobber Jobber is fantastic
I should show you some of the estimates I've been giving they have pictures of everything that I'm
listing it has my best reviews listed at the bottom there's a link for that in the description
too catch y'all in the next one