In today's video, I visit a customer who requested a preventive maintenance. So, I started out, giving him a preventative maintenance and checking everything out, and I quickly realized that there was a problem. His system was abnormally low on refrigerant and compressor was going out on the thermal overload. I performed a thorough leak search and only found a very small leak. So, I offered to charge it up for him. I hope you enjoy the video.
Hey guys, as you see in the weather behind me,
he must really have to pee because I'm telling you,
he does not like coming out in the rain.
The weather you see behind me has made it hard to work today.
I did try to do a preventive maintenance.
I actually tried to do a couple calls
and this one started out as a preventive maintenance.
I thought everything was going to be fine
and I quickly found out that it was a little bit more.
Stay tuned.
Good, how you doing?
We're going to get this maintenance knocked out for you.
All right.
Has anything happened since the last time we were here?
No.
Not working or anything like that?
No problems?
No problem.
Okay.
You're doing pretty good.
And I'm going to go up in the attic
and check things out up there
and then we're going to check things out, okay?
Outside.
Ooh, we got a light.
Already recommended the plug switch to him.
And I think he agreed.
And we just said we'd come back
and do it during preventive maintenance.
Okay.
We have blue wire nuts.
We have a Broad Ocean X13 motor.
I do not like the blue wire nuts.
It looks like we had 10 KW on this one.
And that's a lot of amps to be going through a wire nut.
Yeah, that's 10 KW.
Go power real quick.
One of the things I want to check is this blower motor.
What to do is make sure if I have 10 KW
on a older heat pump like this,
you want to make sure that that 10 KW works.
Hold on, I've got the power disconnected.
Okay, fan is starting up.
I am not seeing heat strips come on.
Let's give it just a second.
I do have red jump to yellow.
Excuse me, red jump to white.
There's a little yellow line on my red right here
because of that float switch.
Let's watch it.
Okay, we have a heat relay.
And it looks like my two wires are purple and orange.
My low voltage wires that go to the top
of that heat relay back in the back.
And those wires are right here.
Let's test them and see if we're actually
getting a signal.
I was afraid I was not getting a signal through here,
but it looks like we might be.
I want to make sure I'm getting 24 volts
all the way to here, and I'm not.
I'm getting 5.2.
I'm still just getting 5.1 amp volts there.
29 volts.
All right, now how is that possible?
Hold on just a second.
All right, I have 29 volts here,
but I'm only getting 12 right now.
All right, that's just not making any sense
unless there's something wrong with my little clip here.
Okay, now I think there might be something wrong
with my alligator clip, my jumper.
This does not want to cooperate, y'all forgive me.
Okay, now I got 27.
And look at here, I immediately get 21 amps.
Oh, I see now.
That has been deactivated for some reason.
It looks like the wire's big enough.
I'm gonna leave it like that, though.
If I got, if it's set up for one heat strip
and one is working, I'm gonna leave it.
I am currently having to run this in cool.
Man, that compressor does not sound good.
One of the last times we were out here,
we had to add refrigerant.
Compressor's pulling 5.6 amps.
Compressor rated at 16, so that five is very low.
Condenser fan motor, let's say 1.1.
I think that is exactly what it is rated at.
I'm showing a power factor of about 0.82.
While it's running, I'm gonna go ahead and check pressures.
This line does not feel very hot,
because that power factor just basically tells me
that it's not running very efficiently.
I think I need some new O-rings.
Woo, that compressor just shut off.
What I want to check is that.
Let me get some of my tools.
That start capacitor, this one over here,
and the start relay really should not have much
of an effect on the compressor when it is running.
It does help it when it's starting,
but when it's running, that's a different story.
That relay and this capacitor are not in the circuit
when it's running, so it won't really affect it.
At least not while it's running.
This is supposed to be a 45 and five.
My 45 is reading, man, I can't see that at all.
42.75, let's do this one again.
42.7 and this one, 4.79.
Neither one of those are low enough
for it to stop the compressor.
I am skittish about putting my fingers on these things.
I am pretty sure we're gonna open up the top
and find that the compressor is going out
on thermal overload.
There's one way we can check it right here
without having to pop the top.
If that compressor is out on thermal overload,
that will not have continuity with that one.
Because of a thermal disc inside the compressor,
it disconnects the wires.
So what I'm gonna do is switch this to beep,
test for continuity.
One here and one there.
That compressor is out on thermal overload.
I'm gonna verify by taking the top off
and sticking my fingers down in there just to feel it.
I could pretty much tell before,
just by the temperature of this pipe right here,
that it was not really getting cold.
So I think we have bigger problems.
I found it.
It's the small things that make me happy.
Okay, my test is to touch that and see if it's hot.
It just went out on thermal overload, I suspect.
So I can feel the heat without touching it.
Really hot, really hot.
The reason that the compressor went out
on thermal overload while it was running,
the reason that's significant
is because if it doesn't have enough refrigerant
coming back to it, cool refrigerant,
that helps cool it off and it's just kind of down there,
dry spinning, that compressor can do that.
So that is a sign, something just bit me.
That is a sign to me that the refrigerant
is much lower than I thought.
Only way to really check that
is to cool off the compressor and check pressures.
Oh, let's kill power.
And of course, that type of disconnect comes apart
when you pull out the pullout.
This shirt I'm wearing, I'm not even real sure what kind.
You'll see how thin that is.
It is extremely warm though.
I thought it'd be cool enough today
to wear something like this.
Another one right here.
Let's see it.
There we go.
Yes, that coil has been replaced.
There are a couple of reasons I know.
One, it's aluminum.
This piece right here is supposed to go underneath
and that piece right there is supposed
to be screwed to the top and it is not.
So I'm gonna try to do a leak search here
to see if I can confirm that my suspected leak is in here.
Unless it's a new coil.
See if I can pick that up over here.
All right, let's try this again.
That's pretty consistent.
But I'm in the very bottom of that drain pan.
If there's anything there,
that is the most likely spot to find it.
So we'll work for those screws.
Turn off that beep.
I do not see any signs of oil anywhere.
That accumulator over there might be a problem.
All right, I'm gonna put this on high.
And you get dirt down in there.
Okay, when I put power back to this,
the compressor had cooled off and it started to come on.
So now I can check pressures
and confirm what I think,
that this thing is very low on refrigerant.
All right, that suction's getting pretty low.
About 80 PSI of suction.
Let's tell it what kind of refrigerant we have.
Sub-cooling's not bad.
Superheat is high.
That suction pressure is low, though.
This customer may not be able to afford a new system
or a new coil right now,
so I'm gonna offer to charge it up.
It's been about a year since last time, so let me know.
I am not reading my sub-cooling,
but right now I'm gonna leave it right there at that.
13, 12 degree superheat.
Finally.
I do intend on working up an estimate
for a couple of things that I found,
like possibly replacing that dual capacitor,
adding a float switch in the primary drain,
but you know, he's got bigger problems
to worry about right now,
and the poor guy's, I mean,
there are other things going on with him,
so I think we did the right thing.
Charge him up, get him going,
and hopefully it'll last him
until things are more stable with him.
I do hope you enjoyed the video.