New Contactor लगाने से पहले हमें कौन कौन सा Specification जरूर देखना होता है @ElectricalTechnician

Electrical Technician
42 followers
Nov 19, 2024
Friends, one of my students sent me these two
images where he asked me this question that
this contractor has
burnt due to excessive current flow,
now this contractor has to be replaced
and to replace that
contractor,
Now his question was, is
this contractor
proper according to the specification or
not, that means, is the
load that will be connected to make the motor run
according to that load? Is this
contractor proper or not, so
I told him the answer to his question,
then I thought why not
tell you also that if you have to
connect any device
with any contractor then you should install it.
What is the specification of the contractor that
you have to see,
let me share all those things with you as you will see,
here I have an old
contractor which is made by Snyder company,
this contractor
got burnt, now if it If we have to replace, then
this contractor has been selected,
so let us understand a little about the specifications of this contractor,
after that we will understand
whether we can use this contractor
in place of this contractor.
To understand whether it can be done or not,
I have made a new slide here
where I have told you the complete
specifications which
specifications you have to see
whenever you go to select a contractor
or go for replacement. So first of all
you have to see
what type of contractor is this.
Above this contractor you will see that
AC Contractor is written here. AC
Contractor means that
we can connect that contractor with AC power supply.
After this, the next specification is
its operating voltage. Operating
voltage means that
we supply power to start the contactor,
as you will see, this is the contactor, the
coil of this contactor, both of them
supply power to us on these two terminals. We have to pay only
when our contractor starts working,
so we will have to see how much power supply we have to give.
Suppose
your old contractor, like
this one, works on 415 volts
and if you are a new contractor, it works on 230
volts. If you take it in this condition, you will have to
change the control wiring and the control wiring, so that such problem does
not arise, you have to
see its operating voltage here,
after that
in your contractor. You will
also get to see the rated operating voltage here.
You get this voltage written here.
Now in detail,
what does it mean? What is the rated operating voltage? Let
me explain to you a little.
Look at any device. When it is run,
a power supply is given in it,
like the motors used in India are
415 volt or
single phase 230 volt,
now if you go to any other country, then
there There is an operating voltage like
in Dubai, 380 volt power supply is
used, in Dubai it is 380 volt,
in India it is 415 volt,
for three phase power supply, then the
operating voltage to run your motor is You will have to see what it is
and whether your contractor has been designed according to that voltage or
not.
You will also have to see that
at the present time,
three different voltages are given here to operate this contractor, such as You will
see that here we can use 220 volt, 380 volt and
660 volt power supply, which
means that maximum we
can use 660 volt power supply, there will be
no problem in the contractor,
if you have more voltage than this then
in this condition.
We cannot use this contractor, after this comes the rated current,
here comes the rated current which is most
important. If you go to select any device,
in electrical, we mostly
look at the current only to see how much
ampere of current we are making to flow.
In the same way, you will have to see
how much ampere current can flow in this contractor.
You will get this detail here in the name of IE.
If you get to see the symbol by doing IE,
then you will understand that this
contractor who Right, the rating of that contractor has been
mentioned. Now
if you look at this contractor, instead of
IE here, 3
ampere rating has been given here, like 18 18
10.6. Now what does this mean? Are we here at
10? You can make the maximum current of 1 ampere flow
or you can make the maximum current of 18 amperes
flow. See the current that happens,
this current keeps changing depending on our voltage.
As you know,
if we increase the voltage then our current decreases.
Similarly, the specification of the contactor
also changes,
if you
use a 660 volt power supply with this contactor, then
in this condition you can get a maximum current flow of 10.6 amps,
but if you
use only If you use 220 volt power supply
or 380 volt
power supply, then you
can get 18 amps of current flow. In the
contactor available in India,
you will find 415 volts written here
and accordingly here. The current
will be told in the picture that was sent, it was
sent from Dubai and this is the picture of the
contractor found in Dubai in the name of Adeli Company,
so
there it is 380 volts, so
according to that, the specification is given here.
Apart from this, if you
want to select the contractor according to kilowatts, then
you can see here that you have to
see whether your motor or the
machine for which you want to
use this contractor to operate is suitable for
that machine. You will have to see
how much voltage is being given to operate that motor (
415 Volts, 660 Volts, 1000 Volts)
and accordingly
make a selection here, for example, suppose that
with this contractor If you are
using 220 volt power supply,
then in this condition you can connect only 4 kilowatt load.
If you have a 660
volt machine and motor, then in this condition
you can connect a complete load of 9 kilowatts.
Can mean that the motor of 9 kW
is a machine, we can use
this contractor to switch that motor on and off,
after this we also have to see in the contractor
that the contractor is
our contractor. Which type is ac3? It is
written here that ac3 means
that to run the induction motor,
we are using this contractor to switch the motor on and off. There are
different types of contractors. Come,
all those contractors are used
at different places, like for your
slip ring motor, we
use a different contractor, for induction motor
we use a different one,
similarly, if you want to do fast switching, then use
that. There is a different type of contractor for this,
it has to be used.
In most of the conditions, we have to run the motor
and to get the motor running, you have to use ac3
type contractor.
ac3 is written here
and after this Here also I have
written it separately and shown it to you, okay, so
you have to see this specification also,
after this the thermal current is written 32
amps. What is the thermal current? See,
here on the top of the conductor you get two current
ratings. Here it is written 32,
here it is written 18, now here you will be
confused whether
this contactor is of 32 ampere rating or
18 ampere rating, see the
current rating of the contactor or the current rating
here. In the name of Pay IE, it means that the
maximum current is there, that is, the
rated current of the contactor, that is what
we have here in the name of Pay IE, but what is
our thermal current, thermal current
means that the maximum current is the highest current as
you You can get the flow done so that our
contactor does not get damaged. Here you will find its rating
written as ITA TTH.
TTH means thermal, so if you see
ITA written here then you will understand that the
maximum current that you can draw from this contactor at the
time of switching on and off. The current that can be flowed
is 32 amperes. According to this contractor,
you can get the current of 32 amperes to flow,
so how do you read the name plate on the top of the contractor,
what does it mean, I have
explained it to you. Now friends, here
we have to understand that this
contractor is ours, can we replace this contractor
with this contractor
or not?
Before explaining this, friends, I
would like to tell you that I have all the people. There is
a video course for this. In the video course, I
tell you all the drawings of our
electrical
panels, such as your
ACB breaker, BCB breaker, LT panel,
ST panel.
If you want to learn how to read drawings, then
you can join our course, the
name of which is How to Read
Electrical Panel Drawing. In this course,
I will tell you
how our drawings will be
read. And apart from reading,
if there is any kind of problem or fault in your panel,
then how will you do its tow shooting,
that too
while reading the drawing, you will get the complete details
in that course in this course.
If you want to learn about dual starter
reverse heat starter then
you can join this course. You get a class of only ₹ 2000000
where you are
given basic to basic information.
You can get complete details of the course here. You can read the
class of 8 hours, it is approximately 17 classes,
in this you
get the PDF of the circuit diagram, along with it we
also provide you the certificate, now
I will also show you the certificate, after this
here comes our electrical wiring.
Master Course: If you
want to do circuit building according to the logic, as if
you are given a condition like you have to
make a machine, make a panel and
only you are told that it should be working like this, then
complete
wiring should be done according to that. To learn it,
you can join this course,
after this we have BFD course, if
you want programming of BFD, trouble shooting
wiring, apart from this, if you want to
operate BFD through PLC, if you want
BFD with HI. To
learn how to communicate, you can
join this course and
get complete knowledge about BFD. After this, we have a
PLC programming course.
If you want to learn PLC programming,
then you
can join the PLC course. The value of PLC of Siemens company
is very high,
this PLC is of Delta company,
you can learn it at basic level, but
if you want to go to advanced level, then you have to go for the
company of Siemens company. You will have to
have knowledge, so if
you want to have knowledge of PLC, then
you can join this course also. After this, we
also have a course on PC, if you want to
learn programming and designing of PC, then join
this course. You
can also join the course, I provide you very good knowledge at a very low cost,
all these courses are there,
on our app
you will get the app by the name of Electrical Technician which is available on the platform. By
downloading that app and logging in,
you can enroll in whatever course you want to join.
Apart from this, friends, if you join the course and
complete the course, then we
also provide you a certificate and
certificate. We are ISO certified, which means
that we have taken the certification of ISO
and we provide the same certification to you, which
means that if you join the course, then the
certificate that you are seeing,
we will provide you this certificate
if you join any video course. If you do
and after joining, you watch the complete classes and
learn the complete things, then we will
provide you this certificate online.
After this, if you want to download the PDF of our book
Electrician A to Z Wiring Book, then
this book. It is also available in our app,
from there you
can directly buy it and download it. I have given the link of this book
and all the video courses of ours
in the description. By
clicking on them, you can join the course directly. You
can do this or
you can buy this PDF directly. In this PDF
you get a total of 190 pages
where you have been told about many circuit diagrams.
Okay, now let
us move ahead, here we will talk about So,
we have two contractors here, one is the
old contractor and one is the new
contractor. Can we replace this
contractor
with this one? So let's understand,
see here I have
written the complete specification.
To operate this contactor, it was being operated through 230
volt, 4155 volt and three phase power supply, which
means that
maximum 415 volt was given here to
operate this contactor and it is
mentioned here in this contactor. We
can supply power of 660 volts, which
means that we can use it at this place, which
means that its operating voltage is
high. After this, the second thing was
Kilowatt rating. If you
want to make selection according to Kilowatt, then it is
written here. That for 415 volts, you
can connect a load of 7.5 kilowatts here.
You can connect a maximum load of 7.5 kilowatts,
but in this contractor you will
see that it is written here that in your
660 volts power supply, you can connect 9
kilowatts. Mostly
we connect the load of 415 volt,
then according to 415 we can connect the load of 7.5 5 KV.
After this, the current
rating was told here that it is 18 amps
and this contactor is also ours. It is of 18 amps,
it is of A3 type, so it is also
useful here, that means it is same to same, after that
its thermal current here, its thermal current
is 32 amps and its thermal current is also
given as 32 amps, that means all If something
is same to same then we can easily replace this
contractor
with this one. Friends, if
you have any doubt of this type,
then you can tell me by commenting in the comment box.
On doubt, I will
make a video and explain it completely
in a good way. I hope
that through today's small video,
you would have got to learn something new.