Connecting Solar to the Grid is Harder Than You Think

Industrial electrical equipment
1 follower
3 Video Views·Oct 31, 2024
On June 4th, 2022, a small piece of equipment called a lightning arrester at a power plant
in Odessa, Texas failed, causing part of the plant to trip offline. It was a fairly typical fault
that happens from time to time on the grid. There's a lot of equipment involved in producing
and delivering electricity over vast distances, and every once in a while, things break. Breakers
isolate the problem, and we have reserves that can pick up the slack. But this fault was a little
bit different. Within seconds of that one little short circuit at a power plant in Odessa,
the entire Texas grid unexpectedly lost 2,500 megawatts of generation capacity,
roughly 5% of the total demand, mainly from solar plants spread throughout the state.
For some reason, a single 300 megawatt fault at a single power plant magnified into a loss of
2.5 gigawatts, dropping the system frequency to 59.7 hertz. The event nearly exceeded Texas'
resource loss protection criteria, which is the minimum loss of power that requires having
redundancy measures in place. Another fault in the system could have required disconnecting
customers to reduce demand. In other words, it was almost an emergency. If you lived in Texas
at the time, you probably didn't notice anything unusual, but this relatively innocuous event
sent alarm bells ringing throughout the power industry. Solar plants, large-scale batteries,
and wind turbines don't produce power like conventional thermal plants that make up such
a big part of the grid. The investigation into the 2022 Odessa disturbance found that it wasn't
equipment failures that caused all the solar plants to drop so much production all at once,
at least not in the traditional sense. Instead, a wide variety of algorithms and configuration
settings in the power conversion equipment reacted in unexpected ways when they sensed
that initial disturbance. The failure happened just before noon on a sunny summer day, so solar
plants around the state were at peak output, representing about 16% of the total power
generation on the grid. That might seem high, but there have already been times when solar was
powering more than a third of Texas's grid, and that number is only going up. The portion of the
grid comprised of solar power is climbing rapidly every year, and not just in Texas, but worldwide.
So the engineering challenges in getting these new sources of power to play nicely with the
grid that wasn't really built for them are only going to become more important.
And of course, I have some demos set up in the garage to help explain. I'm Grady,
and this is Practical Engineering. In today's episode, we're talking about inverter-based
resources on the grid. Solar panels and batteries work on direct current, DC. If you measure the
voltage coming out, it's a relatively constant number. This is actually kind of true for wind
turbines as well. Of course, they are large, spinning machines, similar to the generators in
coal or natural gas plants. But unlike in thermal power plants that can provide a smooth and
consistent source of power through a steam boiler, winds vary a lot. So it's usually more
efficient to let the turbine speed vary to optimize the transfer of energy from the wind into the
blades. There are quite a few ways to do this, but in most cases, you get a variable speed
alternating current from the turbine. Since this AC doesn't match the grid, it's easier to first
convert it to DC. So you have this class of energy sources, mostly renewables, that output DC. But
the grid doesn't work on DC, at least not most of it. Nearly all bulk power infrastructure, including
the power that makes it into your house, uses an alternating current. I won't go into the Tesla
versus Edison debate here, but the biggest benefit of an AC grid is that we can use relatively simple
and inexpensive equipment, transformers, to change the voltage along the way. That provides flexibility
between the insulation requirements and the efficiency of long-distance transmission. So we
have to convert, or more specifically invert, the DC power from renewable sources onto the AC grid.
In fact, batteries, solar panels, and most wind turbines are collectively known to power
professionals as inverter-based resources because they're so different from their counterparts.
Here's why. The oldest inverters were mechanical devices, a motor connected to a generator. This is
pretty simple to show. I have a battery-powered drill coupled to a synchronous motor. When I pull
the trigger, the drill motor spins the synchronous motor, generating a nice sine wave we can see on
the oscilloscope. Maybe you can see the disadvantages here. For one, this is not very efficient. There are
losses in each step of converting electricity to mechanical energy and then back into electrical
energy on the other side. Also, the frequency depends on the speed of the motor, which is not
always a simple matter to control. So these days, most inverters use solid-state electronic circuits.
And look what I found in my garage. These are practically ubiquitous these days, partly because
cars use a DC system, and it's convenient to power AC devices from them. I just hook it up to the
battery and get nice clean power from the other end. Haha, just kidding. These cheap inverters definitely
output alternating current, but often in a way that barely resembles a sine wave. Connecting a
load to the device smooths it out a bit, but not much. That's because of what's happening under the hood.
In essence, switches in the inverter turn on and off, creating pulses of power. By controlling the
timing of the pulses, you can adjust the average current flowing out of the inverter to swing up
and down into an approximate sine wave. Cheaper inverters just use a few switches to create a
roughly wave-like signal. More sophisticated inverters can flip the switches much more quickly,
smoothing the curve into something closer to a sine wave. This is called pulse width modulation.
Boost the voltage on the way in or the way out, add some filters to smooth out the choppiness of
the pulses, and that's how you get a battery to run an AC device. But it's not quite how you get
a solar panel to send power into the grid. There's a lot more to this equipment. For one, look at the
waveform of my inverter and the one from the grid. They're similar enough, but they're definitely not
a match. Even the frequency is a little bit off. I will not be making an interconnection here since
I don't have a permit from the utility, but even if I did, this inverter would let out the magic
smoke. A grid-tie inverter has to be able to both synchronize with the phase and frequency of the
grid and be able to vary the voltage of the waveform to control how much current is flowing
into or out of the device. The synchronization part often involves a circuit called a phase-locked
loop. The inverter senses the voltage of the grid and sets the timing of all those little switches
accordingly to match what it sees. So these are often called grid-following inverters. They
synchronize to the grid frequency and phase and only vary the voltage to control the flow of power.
And that hints at one of their challenges. They only work when the grid is up. I've done a video
all about black starts, so check that out after this if you want to learn more. But in general,
inverter-based resources like solar, wind, and batteries can only follow what's already on the
grid. When the system's down, they are too, regardless of whether the sun's shining or
the wind's blowing. That's why most grid-tied solar systems on houses can't give you power
during an outage. There's another interesting thing that inverters do for solar panels,
and I can show you how it works in my driveway. I have a solar panel hooked up to a variable
resistor, and I'm measuring the voltage and current produced by the panel. You can see,
as I lower the resistance, the output voltage of the panel goes down, and the current it supplies
goes up. But this isn't a linear effect. I recorded the voltage and current over the full range and
multiplied them together to get the power output. If you graph the power as a function of voltage,
you get this shape. And you can see there's an optimum resistance that gets you the most power
out of the panel. It's called the maximum power point. If you deviate on either side of it, you
get less power out. In other words, you're leaving power on the tape. You're not taking full advantage
of the panel's capacity. What's even more challenging is that point changes depending on
the temperature of the panel and the amount of sun hitting it. I ran this test again with a few
more clouds, and you can see how the graph changes. So, nearly all large solar photovoltaic installations
use what's called a maximum power point tracker, or MPPT, that essentially adjusts the resistance
to follow that point as it changes with sunniness and temperature. It's really a separate device
from the inverter, but often they're located right next to each other and inside the same housing.
Even this panel came with a charge controller that has this MPPT function, and you can see it
adjusting the flow of current to constantly try and stay at the peak of the curve while it charges
this battery. These can be used for an entire installation, but in many cases, each panel or
group of panels gets its own MPPT because that curve is just a little bit different for each one.
Tracking the peak power output individually can often squeeze a little more capacity out of the
system. Squeezing out capacity is essential to address another challenge associated with
inverter-based resources on the grid, frequency. The rate at which the voltage and current on the
grid swing back and forth is an important measure of how well generation and demand are balanced.
If demand outstrips the generation capacity, the frequency of the grid slows down. Lots of
equipment, both on the generation side and the stuff we plug in, is designed to rely on a stable
grid frequency, so if it deviates too far, stuff goes wrong. Devices malfunction, motors can overheat,
generators get out of sync, and more. It's so important that rather than let the frequency
get too far out of whack, grid operators will disconnect customers to get electrical demands
back in balance with the available supply of power. Called an under-frequency load shed,
things go wrong on the grid all the time, so generators have to be able to make up for
contingencies to keep the frequency stable. Here's the quintessential example, an unexpected loss of
generation. Say a generator trips offline, maybe because of a failed lightning arrester like the
example. The system frequency immediately starts dropping since power demand now exceeds the
generation, and the frequency will keep dropping unless we inject more power into the system.
The first part of that, called primary frequency response, usually comes from automatic governors
in power plants. If we do it fast enough, the frequency will reach a low point, called the nadir,
and then recover to the nominal value. The nadir is a critical point because if it gets too low,
the grid will have to shed load in order to recover. The other important value is called
the rate of change of frequency, basically the slope of this line. It determines how much time
is available to get more power into the system before the frequency gets too low, and there are
several factors that play into it. How much generation was lost in the first place, how
quickly can we respond, and how much inertia there is on the grid. Thermal power plants that
traditionally make up the bulk of generating capacity are gigantic spinning machines. They're
basically a bunch of synchronized flywheels. That kinetic energy helps keep them spinning during a
disturbance, reducing the slope of the frequency during an unexpected loss. Maybe you can see a
problem with a simple grid following inverter. It's locked in phase with the frequency, even if
that frequency is wrong, and it has no physical inertia to help arrest a deviation in frequency.
If we keep everything the same and just increase the share of inverter-based resources, any loss
of generation will mean a steeper slope, reducing the time available to get backup supplies onto the
grid before it's forced to shed load. Larger renewable plants like solar and wind farms are
increasingly required to participate in primary frequency response, injecting power into the grid
immediately when the frequency drops. And some inverters can even create synthetic inertia that
mimics a turbine's physical response to changes in frequency. But there's another challenge to
this. Dealing with an over-frequency event is relatively straightforward. Just reduce the amount
of energy you're sending into the grid. But response to an under-frequency event requires
you to have more energy to inject. In other words, you have to run the plant below its maximum
capacity, just in case it gets called on during an unexpected loss somewhere else in the system.
For a power company, that means leaving money on the table. So in most places, the energy markets
are set up to pay power plants to maintain a certain level of reserve capacity, either through
operating below maximum output or including battery storage in the plant. The last big thing
that inverter-based resources have to manage is faults. Of course, you need protective systems
that can de-energize solar or wind resources when conditions on the grid could lead to damage.
These are expensive projects, and there's almost no limit to the things that can go wrong,
requiring costly repairs or replacements. But for the stability of the grid, you can't have
those protective systems being so sensitive that they trip at the hint of something unusual,
like what happened in Odessa. This concept is usually referred to as a ride-through. Especially
for under-frequency events, you need inverters to continue supplying power to the grid to provide
support. If they trip offline or even reduce power in response to a disturbance, it can lead
to a cascading outage. This is kind of a tug-of-war between owners trying to protect their equipment
and grid operators saying, hey, faults happen, and we need you to not shut the whole system down
when they do. And reliability requirements are getting more specific as the equipment evolves,
because every manufacturer has their own flavor of protective settings and algorithms.
As inverter-based resources continue to grow rapidly in proportion to the overall generation
portfolio, their engineering challenges are only becoming more important. We talked about a few of
the big ones, lack of blackstartability, low inertia, and performance during disturbances.
And there are a lot more. But inverters also provide a lot of opportunities. They're really
powerful devices, and the technology is improving quickly. They can chop up power basically however
you want, and they aren't constrained by the physical limitations of large generating plants.
So they can respond more quickly, and unlike physical inertia that will eventually peter out,
inverters can provide a sustained response. There are even grid-forming inverters that,
unlike their grid-following brethren, can blackstart or support an isolated island without
the need for a functioning grid to rely on. We're in the growing pains stage right now,
working out the bugs that these new types of energy generation create. But if you pay attention
to what's happening in the industry, it's mostly good news. A lot of people from all sides of the
industry are working really hard on these engineering challenges so that we'll soon
come out with a more reliable, sustainable, and resilient grid on the other end.
I build a lot of homemade demonstrations for videos like this one, and I hope it comes across
how much joy it gives me. I love the challenge of making something useful with constraints on
budget and tools, but I've never built a hot air balloon. One of my fellow creators who runs the
NEO channel just released a video on this incredible story of two families escaping East
Germany in maybe the most creative way possible. I don't know about you, but I have to say that
almost everything I watch these days is produced by independent creators. There's just something
really authentic and original about content that hasn't had to go through five levels of
studio executives before it gets made. NEO's episode on the balloon escape is a perfect
example. Just a fascinating story about homemade engineering, including an interview with one of
the men who made the attempt, all set to the beautiful animations they're known for. And if
you want to see it, it's only available on Nebula. You probably know about Nebula now, even if you're
not subscribed. It's a streaming service built by and for independent creators. No studio
executives deciding what gets the green light, no algorithm deriving the content into a single style,
and no ads getting in the way. We just released a huge update that completely redesigned the home
page, making it easier to find new stuff in addition to your favorites. There's tons of
originals and we're always adding creators, so the new categories can help you discover content
related to your interests. My videos go live on Nebula before they come out here, and my Practical
Construction series, where I embedded on a construction site for a year, was specifically
produced for Nebula viewers who want to see deeper dives into specific topics. I know there are a lot
of streaming platforms out there right now and no one wants another monthly cost to keep track of,
but I also know if you're watching a show like this to the end, there's a ton of other stuff
on Nebula that you're gonna enjoy as well. So I've made it dead simple. Click the link below and
you'll get 40% off an annual plan. That means you pay just one time $30 for an entire year's access
at Nebula.tv slash Practical Engineering. Or if you have subscription fatigue but still want to
support what I'm doing, you can get a lifetime membership. Pay once and you have access for as
long as you and Nebula last. Hopefully that's a long time. If you're with me that independent
creators are the future of great video, I hope you'll consider subscribing.
Thank you for watching and let me know what you think.