The condition of the bushings and the overall insulation of power transformers can be investigated by measuring the capacitance and dissipation factor, also known as the tangent delta, or power factor. Aging and decomposition of the insulation, or the ingress of water, increases the losses and thus more energy is turned into heat in the insulation. The level of this dissipation is expressed by the dissipation factor or power factor. The CPC 100 together with the CP TD1 can measure the capacitance and dissipation factor or power factor in laboratories, test fields, and on site.
The condition of the bushings and the overall insulation of power transformers can be investigated
by measuring the capacitance and dissipation factor, also known as the tangent delta or
power factor.
Aging and decomposition of the insulation, or the ingress of water, increases the losses
and thus more energy is turned into heat in the insulation.
The level of this dissipation is expressed by the dissipation factor or power factor.
Various values of bushings show if there have been breakdowns between capacitive layers.
A rise in capacitance of more than 10% is normally considered dangerous.
The CPC-100, together with the CPTD-1, can measure the capacitance and dissipation factor
or power factor in laboratories, test fields, and on-site.
The modular equipment can be transported easily, thanks to its sturdy cases, which can also
be used to place the instruments onto them for working at a comfortable height.
A powerful test voltage source, combined with high-accuracy measuring inputs, allows for
fast, effective, and accurate measurements.
For convenient transport or mobile use, the instruments can be mounted onto a trolley.
Omicron's Primary Test Manager software makes this testing easy.
It shows clear connection diagrams for the different test modes, thereby making test
connections easier and helping to avoid connection errors.
Settings can be entered conveniently with a keyboard and mouse.
The test can be run and supervised by remote control.
The user interface allows the test to be controlled by
entering the voltage and frequency values where the capacitance and dissipation factor
or power factor will be measured, starting and stopping the test,
and supervising the measurement progress and intermediate results.
Prepared test procedures guide the user through the testing process and offer the basis for
comprehensive reporting.
As an alternative to operating via laptop, the test can also be controlled directly from
the CPC's front panel.
The CPC-100 and CPTD-1 can cover a wide frequency range, from 15 to 400 Hz.
Performing these measurements at several frequencies, rather than at mains frequency only, provides
more comprehensive diagnostic information, hence it has been recommended by SIGRI.
Testing the capacitance and dissipation factor or power factor and subsequent corrective
actions can help prolong the lifetime of an expensive power transformer and prevent extremely
costly outages.
Major utilities and service providers rely on Omicron's powerful and accurate transformer test set.