During commissioning, several tests on current and voltage transformers need to be performed to identify manufacturing errors or transportation damages, to verify correct installation and wiring and to measure the secondary burden. If problems occur during the operation of the plant, further tests will be performed to identify the cause of the error. With the CPC 100, many of these electrical tests can be performed on current transformers and voltage transformers with one single device, saving test time and labor costs.
During commissioning, several tests on current and voltage transformers need to be performed
in order to identify manufacturing errors or transportation damages, to verify correct
installation and wiring, and to measure the secondary burden.
If problems occur during the operation of the plant, further tests will be performed
in order to identify the cause of the error.
With the CPC-100, many of these electrical tests can be performed on CTs and VTs with
one single device, saving test time and labor costs.
Supplied by a single-phase power outlet, it can generate up to 800 amps and up to 2,000
volts AC.
On current transformers, usually the ratio and polarity are verified, and burden and
excitation curve are measured.
The Accuracy Limiting Factor, or instrument security factor, is calculated from these
values to ensure that the CT will perform properly in protection or metering applications.
For injection, the CPC's high current output is connected to the primary terminals.
And for measuring, the secondary terminals are connected to the current measurement input.
If the user prefers not to open the secondary CT wiring, the secondary current can also
be measured using a current clamp.
Within seconds, the CPC displays ratio and ratio accuracy, the phase displacement between
primary and secondary current, and verifies the CT's polarity.
The CT burden and its phase angle can also be measured with the same test setup.
Higher current amplitudes of up to 2,000 amps AC can be generated in conjunction with a
current booster.
Supplied from the CPC by a thin 20-meter cable, the booster is placed close to the CT so that
the heavy high current cables are kept short.
In order to assess whether a CT core is adequate for its burden, the CPC can measure its excitation
curve.
During an automatic test run, the CPC displays the knee point voltage and current according
to the relevant IEC, or IEEE ANSI, standards.
Together with the winding resistance and burden measurement, this allows the accuracy
limiting factor to be calculated for protection circuits and the instrument security factor
to be calculated for metering circuits.
After the test, the CPC automatically demagnetizes the CT core and generates a test report from
the results of the measurement.
Besides testing conventional CTs, the CPC can also test non-conventional CTs used in
an IEC 61850 integrated system.
For a potential or voltage transformer, it is crucial that their ratio and polarity as
well as their burdening are correct.
The CPC100 can generate up to 2,000 volts AC for injecting into the VT's primary side
in order to verify its ratio.
During the ratio measurement, the CPC also checks the VT's polarity by measuring the
signal phase angles on both sides.
On the primary side, by measuring the high voltage output signal, and on the secondary
side by measuring the signal of the voltage measurement input.
The VT's secondary signal may be difficult to measure if it is small in amplitude or
when the neighboring parts of the substation interfere with it.
Interferences can be filtered out by injecting a test voltage with a frequency different
from the power system frequency and selectively measuring at test frequency.
The CPC can also be used to verify that the burden is within the specified range of the
VT, allowing it to operate accurately.
The CPC measures the burden by applying a voltage to the VT's secondary circuits and
measuring the load current and amplitude and phase.
Depending on national and corporate policies, the testing of CTs and VTs may also include
power factor and tangent delta measurements, for instance, during commissioning or as part
of a periodic insulation inspection program.
The CPTD-1 can generate up to 12 kV AC and allows the CPC to measure the power factor,
tangent delta and capacitance in order to assess the condition of the CTs or VTs insulation system.
With the CPC, a number of test devices can be replaced since it is able to perform many
tests not only on CTs and VTs, but also on power transformers, circuit breakers, grounding
systems, and many other electrical apparatus as well.