Maintenance and commissioning of protection relays: CMC 256plus

OMICRONenergy
9 followers
Oct 21, 2023
The Reference - CMC 256plus
Maintenance and commissioning engineers regularly have to test protection relays as well as calibrate measurement transducers, energy meters, and power quality devices. For protection relays, testing on site is common practice, whereas the other devices in many cases are sent to a laboratory for calibration, resulting in considerable efforts and costs. In order to cover all test applications and all calibration tasks on site with a single instrument, reliability, powerful output characteristics and outstanding precision must be combined in one instrument.
Get more information: https://www.omicronenergy.com/en/products/cmc-256plus/
Maintenance and commissioning engineers regularly have to test protection relays as well as
calibrate measurement transducers, energy meters, and power quality devices.
For protection relays, testing on-site is common practice, whereas the other devices
in many cases are sent to a laboratory for calibration, resulting in considerable efforts
and costs.
In order to cover all test applications and all calibration tasks on-site with a single
instrument, reliability, powerful output characteristics, and outstanding precision must be combined
in one instrument.
The CMC256PLUS includes four high-precision voltage outputs, which each generate up to
300 volts phase-to-ground, or 520 volts phase-to-phase, or up to 600 volts in single-phase mode.
The high-precision current outputs can provide up to 3x25A, or 1x75A, or 6x12.5A.
Many tests take place at low voltage or current amplitudes.
By automatic range switching, the CMC256PLUS increases the output accuracy of such small
values even further.
Such high accuracy at small signal amplitudes is, for instance, required when testing protective
functions with low switching thresholds such as sensitive ground fault protection or the
reverse power function of generator protection.
It is also needed for meter testing, especially for the creep test, which determines the stability
of the meter.
The overall accuracy of the outputs of the CMC256PLUS allows for comprehensive testing
of energy meters down to 0.2 class.
Here the CMC256PLUS signals can be directly used as a reference without the need of an
additional reference meter.
Using the 10 volt or 20 milliamp analog inputs, calibration of measurement transducers, again
down to 0.2 class, is possible.
Additionally, the CMC256PLUS is ideal for testing power quality devices which normally
require precise voltage sources, but also in some cases, precise currents.
Maximum output frequency of 3 kilohertz for all voltage and current outputs provides sufficient
performance to cover tests with harmonics as defined in the relevant IEC or ANSI standards
for 50 hertz or 60 hertz networks.
The high output voltage range, up to 300 volts per channel, also allows the calibration of
power quality devices which are directly connected to low voltage networks.
Manufacturers of power quality measurement equipment can make use of this device for
the calibration of their products during the development, assembly, and quality assurance
processes.
Many customers use the CMC256PLUS for testing protective relays of all types.
For such protection testing, the CMC can measure the response time of wet or dry contacts with
10 binary inputs.
Measuring these inputs together with the analyzer option turns the CMC256PLUS into a 10-channel
analog measuring and recording device.
Using an Ethernet interface, the CMC can either be controlled with a PC or via a removable
touchscreen display which allows the efficient manual control of standard protection tests.
Because of the display's robustness and its non-reflective design, it is perfect for outdoor
operation.
For instance, for primary injection tests on CTs and VTs or for checking secondary wiring.
Both modes of control are independent from each other, meaning that if the PC is out
of service, the CM control provides backup operation and vice versa.
If the CMC is controlled with a PC, it is connected via Ethernet, either directly through
an Ethernet cable or over a network.
Using this interface, the CMC can also be used for testing systems using the IEC 61850
communications specification, using goose messages and sampled measured values.
Twelve low-level output signals allow the connection of additional amplifiers.
This allows additional output channels or higher amplitude than the CMC256PLUS alone
can provide.
In common with all Omicron's products, the CMC256PLUS is outstandingly rugged.