Impossible Electrical Mystery: 3 Amp Motor vs 60 Amp Power

HVAC GUY
38 followers
Tools I Use 👇👇👇👇
https://www.amazon.com/shop/hvacguy
In this long video I find two 60 amp breakers that were tripped simultaneously, an extremely dirty evaporator coil, and I work my way through finding multiple electrical problems.
#hvacguy #hvac #skilledtrades #bluecollar #airconditioning @DiversiTechCorp @MilwaukeeTool
At this point this is the question.
Did the motor shorting cause those points to weld inside
the relay or did the relay points weld together cause two speeds
to run at the same time and burn up the motor?
hey guys today i have been dodging
rain as y'all can see in the sky
behind me and we have us a no
cooling call this is my third one today i'm glad
to see the no cooling call start rolling in it's
been what some people call shoulder season the slow season
so i'm glad to see the calls coming
in we're supposed to hit 83 84 degrees today yeah
that'll make people turn on their air
conditioner stay tuned
knock knock hey i've come
to see about his air
conditioner yeah mind if i
come in
and see what's going
on has it been doing
anything at all
okay first thing
i see that little
flashing dark spot you see says replace battery
but this is a mechanical switch the blower should
have come on we have a common red
green yellow and white let's find
the air handler and see what's
going on.
Any air
that gets
through
this
right
here is
unfiltered
and that
filter have fallen down
on the bottom. Coil is filthy.
We have us a tripped
breaker. Tell you what I'm
gonna go ahead and turn
this one off and let's pull
this panel off. I was gonna leave it
but if something tripped the breaker there's
a chance we
could have
something
touching.
Somebody left
a bunch of wire
nuts here
this is a
15 kW heat
kit that
is all
the heat
that they
have okay
something
didn't
just
trip the 60 amp right here it seems to have tripped
the um the breaker in the panel as well
let me take a look look
at that real quick
there it is right there
this breaker
on the bottom left
is tripped something to trip like
that makes me think we have
a direct short somewhere if it blew
this one and the other one at the same time i'm going
to put my meter on it's going to beep for
continuity
i'm just
going
to check
the
ground
for a
second
i might
find
something
trip the
breaker
okay these heat strips are doubly isolated
so when i'm testing the ground i'm not actually
testing the heat strips they're isolated by the sequencers here
and on the other side of the relay
so i'm going to test
again i mean something
really had to go
on the trip that breaker
there's a chance we have a uh i think it's called
a power arc where the two legs of power touch
together so i'm looking
for that on some of these connections
and normally would leave a big black
mark but okay this one
was tripped so we're
looking for orange
and yellow to be shorted
together
there is
humming
but a
motor
is not
enough
to trip
a 60 amp
breaker
it's
supposed
to be a 7.5.
It would help
if I change
my meter to the
right setting.
7.0 microfarads.
That's not
enough to kill a motor.
I mean it's not enough
to make a motor stop.
It spins freely.
I spun the
motor
to get it going.
I should have
a rating
on that motor.
Maxim motor
FLA. Four amps.
It was
just pulling six it is very uncommon for a blower motor
to trip a 60 amp breaker but if the motor
shorted power wire to power wire that could do it i
was told to send an estimate for everything that
i see and that i could go ahead and start on the blower motor
so that's what i'm working on we'll
go snatch that motor
out in just a second
speed connected
right here i've
noticed that i'm not
worried about where those wires were connected
and it's because i know how these are wired
through the sequencers and the relays
and when i wire it back up i'll show you that way you don't
have to make
a mistake
when you're wiring
one of these up
more screws see
one right there
is there
another
one yep
unfortunately
for these
this line
set can be
wrecking
away pull
this out i
might be
able to see if the motor has shorted i might be able
to see some black wires through the housing of the
motor i
have one
of my employees
one time try
to change
a condenser
fan motor
and he said he
couldn't get the blade off and yes he was relatively
a newbie he had not cleaned the shaft he had not
sanded it in any kind of way you have got
to clean that shaft up get all
the oxidation off of it all
the rust if you
want the hub
to move over the
shaft it's got to
be clean i'll turn
this a little bit
all right
that just
slid down
that's going
to make
getting
that out
a lot easier
i'm going to
change this battery
i've got that one's in
sideways there's um
bushings right here
i've got some extras
this one's missing
the rubber's all
tore up on this one
the metal bushing
is missing to clean
that i'm pretty confident i'm gonna have a motor
because this is a half horse excuse me that was a
third horsepower and i have a half horse on here i
do believe oh i told you we might be able to see
in the windings some
burnt marks do y'all see
that how black that is down
in there forgive me i got
in some ants earlier
today and i still
feel like they're
crawling all over
me 3.1 amps 60 hertz
240 volts one-third
horsepower where's
my rpms rpm 1050
so we're looking
for 1075 3.1 amps or
higher 120 volts
and i was gonna have a motor
condenser fan condenser fan
because when i just
went and picked up some
motors these are all
ECM motors yep
these are ECMs i
can put in an ECM
but i'm not going to we got
to go get a motor throw
that thing away make
sure they get a real
filter half horsepower i want to show you something
the motor we took out was 3.1 amps
these are 2.7 nameplate only
said one-third horsepower let
me look for another one 282 33
three speed 1075 half horsepower 2.9 blower motor
half horsepower yep we're going let's get two of
them one for the job
and one for stock there
are no reversing wires
on this so uh taking a little
bit of a risk with a 2.9 amp motor let's see how it goes i've
been busy my van is almost never like
this i need to take some time
and organize it i'm not really taking a huge risk with this motor
that 2.9 amps is going to be on high speed
so i can lower the speed and reduce the amp draw
if it's too high i
don't think it will
be right now we need to clean
that don't put it too tight
water
hose
water
hose
won't do
so good
getting
all
that out
always
always
keep
these
they can
save you a little bit of trouble my van is a mess
some of that stuff is just things i need to throw
away or like on pvc
elbows that just need
to be stored away
in the right place
if you don't know
these little bell housings right here that rubber
this there are motor mounts that use that that
don't really mount to the motor they mount here
and have like a cage that goes around the motor
that's what those
are there for if you
haven't seen them
haven't seen any
mounts like that
in a long time i can tell
by this old motor the strap
was right here underneath
the top vents
but i also know it's going to be hard to push
in if it sticks out any more than this right here
it's going to be hard to get past
the line set in the drain is what i'm saying
wires come
out right
in the middle
there that'll
be fine
i'm trying
to keep
this handy
i did pick
up a
capacitor
for it trade
pro american
made yes
it's going
to be green
these are
going to be
totally different aren't they
I mean they're not there we go
that's not so bad I mean these are
not at
an exact
what 120
degrees
I don't
think it
didn't
seem that
way I did
not undo
uh yeah
I did
I undid
a undid a
coil there
okay we want
this to turn
this way
which is
clockwise
lead end and
we're going to look on here by lead end
that's we're calling these the leads your wires the
other side is shaft end almost all of them are labeled as lead end
when you read these pieces
of paper clockwise cw rotation lead end yellow goes to orange
and orange to yellow so we need
to change
it up most
of them
come
counterclockwise
lead
end all
of what
you see
in there
is hair
there is a little bit still left some
of that is rust put your wheel right
in the middle see if i
bring it down here
this shaft has two flat spots
on it you just want to make sure your set screw
goes on the flat spot if you don't
and somebody else comes behind you to try to change the motor
yeah there's going to be a problem
because once that it has a divot in the rounded part
it's not going to want
to slide through that
hub we're on the flat part
i do put these kind of
tight but you can over tighten them that right
there's enough it is possible to tighten them
so much that you deform the shaft
so don't really crank them down
install that where it's legible
these two are technically the same same wire
and both of them are the run winding your capacitor
is always between
start and run this
one's run this brown
one is start there
are rails back there
that has to go slide
in that's what it's
supposed to look
like under over under
over under same
thing over here
it does make
a difference on the
airflow if it's got
a tighter fit
tightening those
down yet
because i want
to be able to get
some of these in
i see one of them
yep i need some
spade terminals let me see if this will reach i'm gonna try
to find me a grommet for that right
there to protect these wires sometimes
when i'm doing installs i put Seal Tite i'm using Seal
Tite so i take these out you see
i have a few of them saved here
first put that in and that is
half inch i'm going
to show you how to hook
this up to a 9340 relay
that's what we have right here
we're going to have two speeds hooked up two speeds hooked up
but you cannot have the same
speeds running at the same time
so i'll explain how we separate those and how it's wired through
this first i'm going to hook up my
run if you ever have to um wire one
of these furnaces from scratch
you just determine which side is run
and which side is common and that will determine where
everything else goes
this run goes over here
on transformer
that is secure first
why don't we try
our high speed remember there
was an issue about the amp amperage
not being the same and we're
going to put this on normally open
on that on that relay and normally
open on that relay is right
here these two contacts are normally open and
this wire if you'll follow it back goes to here
on top of this sequencer that's my M1 sequencer M1
and M2 see these two are connected and that
goes straight to power so this yellow wire right here has power all
the time and that is my common
but you see over here on the other side of the sequencer
when this energizes it passes
this voltage to here and of course energizes heat strip
but it also energizes this blue wire
and that blue wire comes over here
and that we're going to use for normally closed and
which is this one right here
so when green is energized this closes it's
normally open when it energizes it closes
and puts power to this wire and
brings on the blower
but if green is not energized we just have a call on white
this sequencer will energize
and pass voltage on to here and we're going to
leave that on normally closed
and we have two speeds to choose from let's
choose blue.
So these 9340
relays,
this bottom
is low voltage.
This is
normally
open on that set of contacts and that's normally closed.
On these contacts this
is normally closed and that's normally open.
So if the sequencer energizes it's
going to pass voltage on to here unless
your green has low voltage and then this
will close and this one will open
and it'll send voltage through this one. One wire
left and it's this one now we're not going
to use it we use one of these wire nuts here we're just
going to cap it off for right now until we check our amp draw
and make sure that high speed is
going to be good system's fan
is turned off but the blower
is still running i'm checking to see
if it's getting a call
no 24 volts i know it's
been a long journey but
that relay may be stuck
and that might be what burned up
the motor first i'm checking
to see if i have a call on the
bottom of this i have
no 24 volts okay that relay
is stuck at this point
this is the question did
the motor shorting cause those points
to weld inside the relay or did the relay points weld
together cause two speeds to run
at the same time and burn up
the motor 9340 relay i know this one
is
fried
but
they
are
more
dependable
relays
than
what i
call
those
little
point
relay
this is
common 24 volt common
this is my green wire
from the thermostat which
energizes the relay this one
goes to my normally
closed power this is my
normally open power i
need my black wire okay
black wire goes to normally open
when i turn this on it should
not come on making progress
this coil
is not in
the best
of shape
if y'all can
see that
the coil is
starting to
break apart
i spray it
and brush it it's
just not in great
shape i'm gonna
check it outside
okay we're about
to learn if this thing will even
cool i feel it moving some heat
we're about to get rained on
that is nice and cold it
is starting to rain
full 10 sub cooling 9.8
that's good super heat
with it that hot
in there it's over 80 degrees i think
i've already forgotten what would y'all do
would y'all quote a pulling clean
or considering the shape of the coil quote them a new coil
personally i'm going
to recommend just kind of wait and see
this might work if not they're going
to need a new coil because i cannot clean it
in place any better than i just did guys thanks for
watching i know this was a really long one there
was a lot involved if you enjoy these videos like
subscribe like do all that good stuff check out
the store in the corner you can click on it or
you can scan it
and in it i'm trying to put everything i use catch you on the next one