Power transformers transform electrical energy from one voltage level to another - by stepping voItages up for transmission to minimize losses, or down for distribution. During regular operation, and in particular during an electrical fault, power transformers are subject to electrical, mechanical, thermal, and environmental stresses. Therefore, utilities and service providers test power transformers, in order to assess their condition, schedule maintenance work and plan their replacement.
Power transformers transform electrical energy from one voltage level to another
by stepping voltages up for transmission to minimize losses,
or down for distribution.
They belong to the most valuable assets of the utility.
Manufacturing a new transformer and transporting it to site
results in substantial costs.
However, the damage caused by a transformer failure
and the subsequent loss of production may end up costing far more.
Utilities, therefore, try to keep their transformers in operation
for as long as possible.
During regular operation, and in particular during an electrical fault,
power transformers are subject to electrical, mechanical, thermal,
and environmental stresses.
Power transformers are exposed to mechanical stress
during transport from factory to site,
during relocation from one substation to another,
during earthquakes, or during external short-circuit faults.
Transformers have to withstand the stress of operating voltages,
as well as pulse voltages like lightning or switching pulses.
The inner losses, dominantly caused by load current, must be dissipated.
High temperature causes deterioration of the transformer's insulation materials.
Transformer failures caused by these stresses can result in explosions,
subsequent fire, and costly after-effects such as long outages
caused by cleanup and plant repair,
as well as the long delivery times of new transformers.
Therefore, utilities and service providers test power transformers
in order to assess their condition, schedule maintenance work,
and plan the replacement.
The most common electrical methods include measuring winding resistance
and checking the tap changer,
measuring transformer ratio and excitation current,
and capacitance and dissipation factor or power factor measurements.
Measuring the winding resistance and comparing it to factory measurements
allows possible winding damage to be identified.
For instance, winding short circuits or contact problems of the windings,
leads, or the tap changer.
Measuring ratio and magnetization current
helps to identify short circuits between winding turns.
Capacitance and dissipation factor or power factor measurements
are performed to evaluate the condition of the transformer's bushings.
After an electrical failure,
winding geometry and insulation integrity
may also be verified using advanced diagnostic measurements such as
short circuit impedance or leakage reactance
and frequency response of stray losses,
or measuring power factor or dissipation factor over a range of frequencies.
Through periodic and diagnostic measurement and maintenance efforts,
utilities and service providers help satisfy the ever-growing need
for a reliable electrical supply 24-7.