Protection Testing: Measuring and recording analog and binary signals

OMICRONenergy
9 followers
Oct 22, 2023
EnerLyzer is a software option for the CMC 256plus and CMC 356, which enables powerful analog measurement functions. It offers four modes of operation: multimeter, harmonic analysis, transient recording and trend recording. It allows each of the ten measurement inputs of the CMC to be reconfigured for measuring voltages of up to 600 V or, via shunts or current clamps, it can also measure currents.
Get more information: http://www.omicron.at/
Analyzer is a software option which enables analog measurement functions.
It offers four modes of operation, multimeter, harmonic analysis, transient recording and
trend recording.
It allows each of the ten measurement inputs of the CMC to be reconfigured for measuring
voltages of up to 600 volts or, via shunts or current clamps, it can also measure currents.
In multimeter mode, these values can be displayed directly or their products can be calculated.
RMS voltage and current, together with phase angles, as well as zero, positive and negative
sequence components and power values, can all be displayed.
In harmonic analysis mode, Analyzer displays the magnitude and total harmonic distortion
of the overall signal, the magnitude and phase of the fundamental and of each harmonic.
In transient recording mode, it allows the CMC to be used as a powerful ten-channel transient
event recorder.
The CMC can then record voltage and current waveforms and binary signals and store them
in the ComTrade format.
This allows them to be replayed so that the performance of the device under test can be
observed under actual system conditions.
The CMC recording can be triggered by power quality criteria such as voltage sags and
swells, harmonics, frequency or frequency change or other power quality events.
Then the waveform is recorded and can be replayed or used for later analysis.
In trend recording mode, Analyzer records certain quantities such as frequency, current,
voltage, phase angles, real, reactive or apparent power or power factors and displays them in
separate time-segregated diagrams.
Measurements over long periods of time, from several days to several weeks, are possible.