Protection testing made easy: CMControl operating modes

OMICRONenergy
9 followers
Oct 22, 2023
The deregulation of the energy market has led to an increased range of tasks that today's utility engineers are expected to perform. One of these tasks is - of course - protection testing. They need tools that can be operated immediately, even if they are used infrequently. CMControl enables the CMC to be used with minimal preparation.
Get more information: http://www.omicron.at/cmcontrol/
Protection engineers often need to verify that the wiring is correct from cubical terminals
to the relay, between the instrument transformer and the relay, or between the test equipment
and the relay.
This is easily achieved using the wiring checker tool by injecting different currents
into each of the three phases so that they can be identified and ensuring that each current
appears on the correct phase at the relay.
For many relay types, it is essential to be able to exactly determine the pickup value
and the reset ratio.
With the pickup drop-off tool, this is straightforward.
The user simply selects the pickup value to be tested, for instance an overcurrent
starting value and the fault loop.
Now a keypad appears on the touchscreen for entering other parameters such as the voltage
to be applied during measurement of the pickup value.
With the control wheel, the user only needs to increase the desired value until the starting
contact is activated and then reduces it again until it resets.
The reset ratio is automatically calculated.
Many protection tests are performed as test shots consisting of a healthy system condition
before, the fault situation, and finally the post-fault after tripping.
The trip time test tool allows the user to easily perform such tests.
It generates a pre-fault, fault, post-fault sequence, showing the user the actual state
while performing the sequence and indicating the timing of the relay contacts during the
test.
Relays with multiple timing stages, like overcurrent or distance protection, can also be tested.
In the time grading diagram, the user can simply select the value to be tested with
the control wheel and perform the test by pressing the button.
The corresponding value and the trip time are displayed.
The control wheel also allows for the easy determination of zone borders.
For tests not covered by a dedicated testing tool, all amplifiers can be set according
to the user's wishes, in amplitude, phase angle, and frequency.
With the control wheel, values can also be changed during injection.
Multiple selections, such as the amplitudes of two outputs, are also possible, enabling
the testing of a synchronizer function.
The intuitive and straightforward handling of the CMControl software makes it an ideal
tool for anyone who wants to start testing immediately, without the need for any training.