In the factory, winding resistance is measured in order to assure proper manufacturing and calculate conductor losses. On site, this measurement is performed to evaluate possible winding damage, such as short circuits between windings or between turns, open circuits, contact problems and to assess the condition of the tap changer. Winding resistance measurement is one of several methods of transformer diagnostics offered by the multifunctional CPC 100.
In the factory, winding resistance is measured in order to assure proper manufacturing and
calculate conductor losses.
On site, this measurement is performed to evaluate possible winding damage, such as
short circuits between windings or between turns, open circuits, contact problems, and
to assess the condition of the tap changer.
With the CPC-100, current is injected into the winding.
Measuring current and voltage, the CPC displays the resistance value.
Then it updates the value every second and displays the difference between two subsequent
values.
As soon as the inductance of the winding is charged, the resistance value stabilizes to
represent the winding resistance.
After the CPC takes the final measurement, it reduces the test current to zero, discharging
the energy stored in the winding.
A green safety light will be lit as soon as it is safe to remove the test leads.
Based on the measured resistance value, the CPC can calculate the corresponding value
at a given reference temperature.
The winding's condition can be assessed by comparing the measurement results with results
from measurements performed in the factory or during commissioning, or with results from
measurements of other phases.
For tapped windings, winding resistance measurement is usually performed for each tap position.
Besides giving information about the condition of the winding, this measurement is also used
to check the condition of the tap changer, which is connected in series to the main winding.
Results indicate when to clean or replace the tap changer contacts, or when to replace
or refurbish the tap changer, which has a shorter lifespan than the active part of the
transformer.
The CPC makes this measurement easy by combining the resistance measurements for all taps in
one sequence.
Each time the user operates the tap changer, the CPC measures and displays the winding
resistance at this tap position as soon as the values have stabilized.
When all taps have been measured, it discharges the winding automatically and indicates when
the process has been completed.
In addition to this static resistance measurement, the CPC also evaluates the on-load tap changer's
dynamic switching behavior and checks for continuity as recommended by Seagrid.
When switching from one tap position to another, the tap changer's intermediate position via
the commutating resistors make the DC current drop temporarily.
The CPC measures the size and the slope of this current drop.
If all the tap changer's taps are in good condition, this dynamic resistance measurement
will deliver similar results for all taps.
The results of this dynamic resistance measurement can easily be compared across taps using an
Excel template.
Winding resistance measurement is one of several methods of transformer diagnostics offered
by the multifunctional CPC100.