Enhanced transmission network applications

OMICRONenergy
9 followers
Oct 22, 2023
Using GPS or IRIG-B based synchronization, several CMCs can be used together to allow the user to test phasor devices. Synchronizing two or more CMC units, for instance at the ends of a power line, permit the verification of communication-based distance protection schemes, or line differential protection. This end-to-end testing capability is also used by NetSim. The program allows to use the CMC for network simulation.
Get more information: http://www.omicron.at/cmirigb/
Omicron CMC devices are open for many special applications.
To help to prevent system blackouts, phaser measurement units or PMUs have become widely
used.
Using GPS or iRig-B based synchronization, several CMCs can be used together to allow
the user to test these phaser devices.
Using two or more CMC units, for instance at the ends of a power line, permit the verification
of communication-based distance protection schemes or line differential protection.
This end-to-end testing capability is also used by NetSim.
The program allows the use of the CMC for network simulation.
From a digital network model, NetSim calculates the transient voltages and currents occurring
during various network conditions and directly outputs them to the relay.
For instance, short-circuit events on single or parallel lines, including mutual coupling,
three terminal lines, power swings or evolving double faults are possible.
The simulated network may also include a transformer.
NetSim will automatically consider amplitude and vector group.
Since for correct operation of the relaying scheme, the performance of the CTs is crucial,
real CT behavior can also be modeled.
CT parameters may be entered manually.
Alternatively, CT analyzer can determine the parameters and directly export them to NetSim.