A station's switching apparatus and its connections have to handle load currents in the range of hundreds or thousands of amps. Low resistance values at all connection points - circuit breaker and disconnector contacts as well as any joint - assure low power dissipation. Keeping the equipment's temperature within its specifications is a precondition for normal and correct operation over its expected lifetime. The low contact resistance of circuit breakers and disconnector switches as well as any joints can be confirmed by micro resistance measurement.
A station's switching apparatus and its connections have to handle load currents in the range
of hundreds or thousands of amps.
Low resistance values at all connection points, circuit breaker and disconnector contacts,
as well as any joint, assure low power dissipation.
Keeping the equipment's temperature within its specifications is a precondition for normal
and correct operation over its expected lifetime.
The low contact resistance of circuit breakers and disconnector switches, as well as any
joints, can be confirmed by micro-resistance measurement.
The contact resistance can be measured precisely by injecting high DC current and using a four-wire
resistance measurement setup.
Injecting DC current and measuring voltage with a separate set of cables assures that
only the contact resistance is measured, and the voltage drop on the current injection
cables does not influence the result.
The CPC-100 includes a 400-amp DC output and a precise DC voltage input, which can measure
the contact resistance of circuit breakers, disconnectors, and busbar joints.
Integrating micro-resistance measurement into the entire test plan for a feeder allows the
CPC to perform this test effectively.
The same test set that's being used for instrument transformer tests creates one overall test
report covering all the equipment in the feeder.