Testing meters & transducers

OMICRONenergy
9 followers
Oct 21, 2023
Through its outstanding precision, the CMC 256plus can be used for the calibration of many measurement instruments. All common types of energy meters can be tested. Furthermore, the CMC allows simulating power system conditions and thus measuring the output signals of transducers.
Get more information: https://www.omicronenergy.com/en/products/cmc-256plus/
Through its outstanding precision, the CMC256plus can be used for the calibration of many measurement
instruments.
For testing energy meters, the traditional method has been to use a stabilized but not
very accurate power source and a high-precision reference meter for comparison.
The CMC256plus is so accurate that it makes a reference meter unnecessary.
All common types of energy meters can be tested.
With special inputs for registering meter pulses, the CMC allows for closed-loop testing.
These inputs, or the alternative optical scanning heads, allow the CMC to pick up all kinds
of meter pulses, such as LEDs, ferrous disks, or directly from mechanical or TTL outputs.
The CMC allows the output of different load conditions to simulate any load point, such
as 50% nominal current, various power factors, and many other conditions.
It allows the performance of load, no load, creep, and mechanism tests on all types of
electromechanical or digital energy meters, as required by the relevant standards.
For testing special operating conditions, the device can also generate currents with
a superimposed DC component or harmonics.
The CMC can test precision meters with pulse rates as high as 100 kHz.
At the end of the test, the CMC will provide a report containing the accuracy and pass
or fail information for each test point.
The CMC256PLUS allows the calibration of measurement transducers for voltage and current, active,
reactive or apparent power, power factor, and many other quantities.
It can also test multipurpose transducers, combining several of these functions into
one device.
The CMC allows simulating power system conditions and thus measuring the output signals of transducers.
Transducers to be tested include those with linear, compound, or quadratic characteristics.
The test points to be used are defined in a table.
During the test, the CMC compares the nominal behavior with the actual measured values.